ADDRESSABLE
FIRE ALARM PANEL
ci
i
m
p
l
i
S
y
t
Micro
INSTRUCTION MANUAL: 32 Device,4 Zone Addressable Fire Alarm Panel
Approved Document No: GLT.MAN-129
PAGE 16
Issue : 1.0 Author: NRPJ Date: 11/04/2008
POINT DISABLEMENT
The Simplicity Plus panel can also disable individual devices (detector,
call point, sounder or interface). To do this, enter CONFIGURATION
MENU 2 and select EDIT DEVICE. Select the required device, then
press GENERAL DISABLEMENT button. The Device label now flashes
between the programmed label and Device Disabled. The general
disablement LED will also be lit. This device is now disabled.
To re-enable the device, press the disable button again. Note that the Zone disablement LED for this
address will not light because this would suggest that the whole zone is disabled, so would be
misleading.
VIEWING DISABLEMENTS
There are two ways to check for disablements: from the Disablement screen, or from the device status
screen.
To view from the disablement screen
Press disable, then press NEXT to scroll through all the zones & sounders.
If there are no disablements, the screen will show
If the whole zone is disabled, the screen will show
If there are one or more disabled points in this zone, the screen
will show.
(TIP: a quick way to enable several disabled points is to
disable the zone, then re-enable it)
To view from the Device Status screen
Press enter then option 2 to select Device Status
If a device is enabled, the screen will show
If a device is disabled, the screen will show
(Note that line 3 will flash between the device label and
Device Disabled Message)
If a device is in a disabled zone, the screen will show
(Note that line 3 will flash between the device label and
Zone Disabled Message)
Zone Disablement
Zone 1
Disabled
Single Devices: 0
Zone Disablement
Zone 1
Enabled
Single Devices: 0
Zone Disablement
Zone 1
Enabled
Single Devices: 2
Optical
Analog: 25 Normal
Fl 3 Bedroom 303
Zone:01 Ad:016
Optical
Analog: 25 Normal
Device Disabled
Zone:01 Ad:016
Optical
Analog: 25 Normal
Zone Disabled
Zone:01 Ad:016
Optical
Analog: 25 Normal
Device Disabled
Zone:01 Lp:1 Ad:016