ADDRESSABLE
FIRE ALARM PANEL
ci
i
m
p
l
i
S
y
t
Micro
INSTRUCTION MANUAL: 32 Device,4 Zone Addressable Fire Alarm Panel
Approved Document No: GLT.MAN-129
PAGE 24
Issue : 1.0 Author: NRPJ Date: 11/04/2008
Specifications
Electrical Specifications
ELECTRICAL DESCRIPTION
VALUE
MAINS VOLTAGE
230V AC +/- 10% @ 50/60 Hz
BATTERY VOLTAGE
24V DC (2 X 12V,2AH SLA BATTERY)
CHARGER SIZE
1 AMP
LOOP VOLTAGE
27V DC NOMINAL (+9 volt data)
AUXILIARY FIRE OUTPUT
1 x RELAY SELV (1A MAX)
FAULT OUTPUT
1 x RELAY SELV (1A MAX )
NUMBER OF ZONES
4
MAXIMUM ZONE CAPACITY
8 DEVICES PER ZONE
SOUNDER ALARM OUTPUTS
LOOP POWERED SOUNDERS ONLY
MAINS FAILED CURRENT (BUZZER ON)
39mA
MAINS FAILED CURRENT (BUZZER OFF)
37mA
MAXIMUM LOOP RESISTANCE
25 ohms
MAXIMUM LOOP CAPACITANCE
0.3
μ
F
MAXIMUM VOLTAGE PICKUP ALLOWED
50mV
LOOP SHORT CIRCUIT PROTECTION
540mA
CHARGER VOLTAGE
28.3V @ 22-24
o
C (NO BATTERY)
CHARGER SHORT CIRCUIT PROTECTION Batteries less than 20V
Enclosure Specifications
DESCRIPTION
VALUE
ENCLOSURE SIZE
355 x 275 x 70 mm
TOP CABLE ENTRIES
5 x 19mm KNOCKOUT ENTRIES
BOTTOM CABLE ENTRIES
NONE
REAR CABLE ENTRIES
NONE
Fuse Ratings
FUSE NO
DESCRIPTION
RATING
FS6
Charger Fuse
2.0A Fast Blow 5 x 20mm glass
FS5
Battery Fuse
800mA Fast Blow 5 x 20mm glass
INLET FUSE
Mains Protection Fuse
2A Quick Blow HBC 5 x 20mm ceramic