INSTRUCTION MANUAL: 32 Device,4 Zone Addressable Fire Alarm Panel
Approved Document No: GLT.MAN-129
PAGE 25
Issue : 1.0 Author: NRPJ Date: 11/04/2008
Simplicity Micro Configuration & Testing
Record the device label for each device in the chart below. If a detector has a base
sounder fitted , mark the column with a tick or a “Y”. Test each detector for Alarm
operation (Eg With smoke Spray), and for fault reporting (by removing the detector).
Check that each sounder operates in alarm. (Mark with P for Pass)
Site Name:
Site Address:
Installation
Date:
Installed
by:
Service Contract: (Y/N)
Tel:
Addr Device
Type
Sounder
Base
Detector Name
Fire
Test
Fault
Test
Sounder
Activate
Eg Optical Y Hallway
P P
P
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32