ADDRESSABLE
FIRE ALARM PANEL
ci
i
m
p
l
i
S
y
t
Micro
INSTRUCTION MANUAL: 32 Device,4 Zone Addressable Fire Alarm Panel
Approved Document No: GLT.MAN-129
PAGE 4
Issue : 1.0 Author: NRPJ Date: 11/04/2008
Mains & Battery
Connecting the mains.
The Mains supply to the FACP is fixed wiring, using
Fire resisting
3-core
cable (Between 1 mm² and 2.5mm²) or a suitable 3-conductor system, fed
from an isolating double pole switch fused spur, fused at 3A.
IT SHOULD
NOT BE CONNECTED THROUGH AN RCD.
This should be secure from
unauthorised operation and be marked ‘FIRE ALARM: DO NOT SWITCH
OFF’. The supply must be exclusive to the Fire Panel.
MAKE SURE ANY
SPARE ENTRY HOLES ARE COVERED WITH THE GROMMETS
PROVIDED
Connecting the batteries
The Simplicity Micro requires 2 x 12 V sealed lead acid (SLA) batteries
The two batteries are wired in
series
.
The
+ve
of one battery is connected to the
red
battery lead.
The
–ve
of the other battery is connected to the
black
battery lead.
The –ve of the first battery is connected to the +ve of the second battery using
the link wire supplied.
Although there are many sizes of suitable battery, the sizes the enclosure has
been designed for 12V 2Ah.
SLA BATTERY
12V / 2 Ah
TO PCB
2 x 2Ah Batteries
BATTERY
INTERCONNECTING
CABLE
SLA BATTERY
12V / 2 Ah