7. DISABLEMENTS
7.1 REASONS FOR DISABLING CERTAIN PARTS OF A FIRE ALARM SYSTEM
Certain parts of this Fire Alarm Panel can be temporarily disabled (i.e. switched off) to suit prevailing conditions. For example, if
there is a risk of a False Alarm in a zone, for example, from vehicle exhaust smoke in a loading bay, it is possible for the user to
disable that zone during the risk period and then enable it again afterwards. During a disablement of a zone(s), no fire or fault signal
will be processed for that zone(s). Only zone(s) in a non-alarm state can be disabled, that is zones already in a fire condition cannot
be disabled.
External sounders can also be disabled as could be required in certain conditions
7.2 TO DISABLE A ZONE AND/OR EXTERNAL SOUNDERS
1.
Enter user access code 123;
2.
Press GENERAL DISABLEMENT button a
3.
The panel will prompt for disablement code (248)
4.
The screen will then show: ZONE DISABLEMENT ZONE 1. The panel is now in SELECT
DISABLEMENT MODE.
5.
Press NEXT BUTTON until the required zone or sounder circuit is DISPLAYED. Press
ENTER to confirm the disablement.
The screen will now show that the zone is disabled, and the GENERAL
DISABLEMENTLED will light. This section is now disabled.
Zone Disablement
Zone 1
Zone Enabled
Disabled Devices: 0
Zone Disablement
Zone 3
Zone Disabled
Disabled Devices: 0
6.
If more than one zone (or sounder) needs to be disabled, then press DISABLEMENT SELECT again until the required zone
(or sounder) is selected.
7.
If the panel needs to be taken out of SELECT DISABLEMENT MODE (e.g. to silence a fault on another part of the system),
press the CANCEL button.
7.3 TO ENABLE A ZONE AND/OR EXTERNAL SOUNDERS
1.
Enter user access code (123 if required)
2.
Press GENERAL DISABLEMENT button
3.
Enter disablement code (248 if required)
4.
The screen will show: ZONE DISABLEMENT ZONE 1. The panel is now in SELECT DISABLEMENT MODE.
5.
Press NEXT until the disabled Zone or sounder is shown.
6.
Press ENTER to enable the selected item. The screen will now show enabled. The General Disablement LED will turn off
after all sections are taken out of disablement.
7.
Press Cancel to return the panel to normal operation.