INFINITY ID2 INSTALLATION MANUAL.
Software Versions: PANEL 1.N & LOOP O.N
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ Date: 06/04/2016
PAGE 9
6.2 First Fix
6.2.1 MOUNTING THE FIRE ALARM PANEL
The ID2 comes with many cable entry holes. If another entry hole is required, it is strongly recommended that
the, the termination PCBs should be removed and stored in a safe place. This would also help while fixing the
back box to the wall.
6.2.2 FIXING THE BACK BOX TO THE WALL
Figure 2: Plan view inside the enclosure without PCBs. Side view for surface installation.
Note that the enclosure has a document tray on the left hand side that holds the panel manuals. If semi
flushing or fitting to a tight space, remember to remove the manuals before fitting to the wall.
Fix the enclosure to the wall using the three mounting holes provided.
Check the build & condition of the wall to decide a suitable screw fixing.
The mounting holes are designed for No 8 roundhead or countersunk woodscrews (or similar).
Remove any debris from the enclosure.
Take care not to damage the FACP during installation.
6.2.3 PLANNING CABLE ENTRY
Fig.2 above shows the location of the cable entries to facilitate planning of wiring (home runs) to be brought to
the panel.
The 230Va.c. Mains cable must be fed into the enclosure via one of the cable entries at the top right corner of
the back box. (Refer to “Connecting the Mains” on Following Page).