INFINITY ID2 INSTALLATION MANUAL.
Software Versions: PANEL 1.N & LOOP O.N
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ Date: 06/04/2016
PAGE 11
6.2.5 CONNECTING THE BATTERIES
Figure 4: Battery location and connection details
Although there are many sizes of suitable battery, the sizes we usually recommend
for the ID2 are 12V 7Ah,
To calculate the exact requirement, use the equation in section 20.1, STANDBY
BATTERY CALCULATIONS
The two batteries are wired in
series
to give
24 Volts
.
Connect the
–ve
of Battery 1 to the
black
battery charger lead.
Connect the
+ve
of Battery 2 to the
red
battery charger lead.
The +ve of the first battery is connected to the -ve of the second battery using the
FUSED link wire supplied.
When fitting the batteries, take care not to damage the temperature monitoring
thermistor.
(Next to the charger lead connections).This is used to prevent
overcharging the batteries in high ambient temperatures.
Recommended Batteries
Powersonic PS-1270, 12V, 7Ah (or equivalent)