INFINITY ID2 INSTALLATION MANUAL.
Software Versions: PANEL 1.N & LOOP O.N
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ Date: 06/04/2016
PAGE 13
7.1 Specific device wiring instructions
All products will come with their own wiring instructions. This should be used when connecting a product. But as a general
guideline, here are the connection details of most Zeta Addressable products.
7.1.1 CP3/AD Manual Call Point
The CP3/AD call point has a built in isolator which can be wired in circuit or not used. This is done by means of not
wiring to the negative out terminal on the call point. The following terminals are used for connecting the call
point.
2 x Negative in terminals (note if you only connect to the negative in terminals then the isolator is bypassed)
1 x Positive in terminal
1 x Positive out terminal
1 x Negative out terminal (note if used puts the isolator in circuit)
1 x Earth terminal used to connect the cable screen
7.1.2 MKII detectors (All types) Base connection
Negative out
terminal used
when isolator is
required
Protocol setting
jumper link must
be removed for
MKII protocol
The connection for the detectors
bases is made as follows:
Terminal L1IN is –ve (Blue)
Terminal L2 is +ve (Brown)
These are the only two
connections required.