INFINITY ID2 INSTALLATION MANUAL.
Software Versions: PANEL 1.N & LOOP O.N
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ Date: 06/04/2016
PAGE 23
11 OTHER CONNECTIONS
11.1 Repeater connection
The ID2 has an RS485 connection for a serial repeater. The repeaters have full control. Up to 2 repeaters can
be powered from the Aux24V DC output on the panel. If 3 or more are to be connected, then they must be
powered from external 24V power supplies. The panel supports up to 8 repeaters.
ID2 PANEL
ID2 REPEATER
ID2 Panel
ID2 Repeater
Description
AUX 28V +
24V DC IN +
Power for repeater
AUX 28V -
24V DC IN -
Power for repeater
RS485 B
RS485 B
Data connection
RS485 A
RS485 A
Data connection
RS485 GND
RS485 GND
Data connection screen