INFINITY ID2 INSTALLATION MANUAL.
Software Versions: PANEL 1.N & LOOP O.N
Approved Document No: GLT-211-7-1
Issue 1.9 Author: MG/NJ Date: 06/04/2016
PAGE 30
15 VIEWING PANEL INFORMATION
15.1 Menu Structure
To help locate the different features available, the menu structure of the ID2 panel is shown here.
MENU LAYOUT
MAIN MENU
SUB MENU 1 SUB MENU 2
DESCRIPTION
CONFIGURATION MENU 1 – THE USER MENU
1:Clock
-
-
Set the date and time
2:Logs
VIEW EVENT LOG
1: Alarms
-
View all fire alarm events
2: Faults
-
View all fault events
3: System
-
View all other events (eg User access, menu
access, clock change, etc)
4: All
-
View all events
3:Devices
-
-
View device type and zone / ID information as
well as any text labels
4: Engineer
-
-
Puts the panel into Engineer menu 1
ENGINEER MENU 1 – THE ENGINEER MENU
1:Zones
1. Zone
Summary
-
View the zones and shows how many devices
are fitted to each zone
2. Configure
Now
Configure the Zones
2:Panel/Zone Text
-
-
Set Panel Name and Zone Label
3:ID Device
-
-
* Edit device label
(Press ENTER)
* Turn on alarm LED / Flasher
(Press 4)
* Ring sounder
(Press GENERAL TEST)
* Select alarm verification
(Press 8)
* Configure Sandwich Sounder Base
(Press 7)
* Disable this device.
(Press General Disable)
* Configure I/O OUTPUT
(Press 8)
* Configure I/O INPUT
(Press 6)
ENGINEER MENU 2
4:Alarm Verify
1:Verify Time
-
Detector verify time (1:00 – 3:45)
2:Choose
Devices
-
Select the device that requires verification (this
can only be set to a smoke detector)
5:Config Alarms
1:Relay
-
Edit the way the fire relay works in an alarm
condition (Common, Manual, Detector)
2:Interfaces
-
Edit the Interfaces work in an alarm condition
(Common, Zonal detector, Zonal all, own input,
panel link, Manual alarm, Detector alarm, Zonal
MCP)
3:Alarm Tone -
Change the sounder output tone (there are 16
different tones)
4.Resound
Sets whether sounder operate for any new
alarm, an alarm from a new zone, or only for the
first alarm. (EN54 Requirement)
6:Misc
1:Language
Select the panel language (there are 5)
2:Version
Shows the panel and loop software version
3:Topology
Changes the panel from Radial wiring to Loop
Wiring
6:Reset
Reset the event log and restore back to factory
default settings (Requires the code 159)