INFINITY ID2 INSTALLATION MANUAL.  

 

 

Software Versions: PANEL 1.N  & LOOP O.N 

 

Approved Document No: GLT-211-7-1

 

 

 

 

Issue 1.9    Author: MG/NJ     Date: 06/04/2016

 

 

PAGE 38

 

19.4 Supply faults 

 

FAULT MESSAGE 

Caused by 

Remedy 

BATTERY FAULT 

Loss of Battery power  
 

Check “battery fuse 2A” is intact. 
Check that battery connections are secure 

POWER SUPPLY FAULT 

Loss of Mains power 

Check that main power is present. 
Check that PSU cage has output healthy LED on 
Check  cables  from  PSU  cage  to  PCB  are  fitted 
securely 
Check Power in fuse (fuse 800mA) is intact.   

LOW BATTERY FAULT 

Low Battery voltage detected  
 

Check battery voltage. (should be 26-27V) 
Check  that  2  x  12v  batteries  are  connected  in 
SERIES) to give 24V 
If there has been a recent mains failure, leave the 
batteries charge for an hour or so to see if the fault 
clears. 

CHARGER FAULT 

Failure of Charging circuit 

Remove all power. Wait for 10 seconds then 
reconnect power. If fault returns, the charger 
circuit has been damaged, and the PCB will need 
to be repaired or replaced. 

BATTERY HIGH 
IMPEDANCE 

Bad Batteries Detected 

Check that the battery fuse is rated as 2A, and 
that it is fitted securely (Other fuse ratings can 
sometimes give a bad reading) 
Check Batteries with a load test meter to confirm 
the batteries are bad, and replace if necessary. 
Check battery terminals are clean, and make a 
good contact with the battery leads. 

 

 

 

 

19.5 Earth faults 

 
An EARTH fault indicates that something is shorting to earth 
(usually through the cable screen). Disconnect the earth  
screens one at a time to determine the problem line. 
 
(Note: connecting other equipment, eg an oscilloscope or a PC, to  
the panel can give an earth fault) 
 
The  Screen  will  indicate  if it  is  a  Positive or  Negative  voltage  shorting  to earth  (Earth  Fault  Pos  or  Earth  Fault 
Neg). 
 

***DO NOT DISCONNECT THE MAINS EARTH CONNECTION. THIS WILL CAUSE A PROBLEM WITH THE 
PANELS OPERATION***

 

 

19.6 Double address 

 

This  indicates  that  a  double  address  has  been  detected.  This  usually  happens  during  initial  setup,  where  2 
detectors  are  given  the  same  address,  or  if  a  head  is  replaced  during  maintenance  and  its  address  has  been 
wrongly set. In the second scenario, the panel will report 2 fault addresses, one will be the double address, and 
the  other  will  be  a  missing  device.  As  a  further  aid  to  finding  the  fault,  the  panel  will  light  the  LEDs  of  any 
detectors  with  a  double  address  (Sounders  &  I/O  units  will  not  be  indicated  as  they  have  no  panel  controlled 
LED to light up) 
 

1.  Make a list of the double addresses reported (there may be more than one). 
2.  Go  to  view  device  screen  in Configuration  menu 1.  Scroll through  the devices, and make  a  list  of  any 

that are missing (

Note

: the panel skips over empty addresses when scrolling) 

3.  Go  to  the  location  of  the  missing  device,  and  check  if  it  has  its  LED  on  (Detector),  or  check  the  dip 

switch setting. 

4.  If this does not cure all double addresses, go to the known location, and temporarily remove the device. 

The  panel  will  now  report  the  type  of  device  that  was  also  configured  to  this  address  from  the  view 
device  screen.  This  will  help  narrow  down  the  search  for  the  device.  (eg  if  extra  device  is  call  point, 
check the address settings of all the call points) 

 
 
 
 

  ***  FAULT  *** 
       1 of 1 
 

    Earth Fault Pos

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for ID2/4

Page 1: ...ware Versions PANEL 1 N LOOP O N Approved Document No GLT 211 7 1 Issue 1 9 Author MG NJ Date 06 04 2016 INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM WITH ID TECHNOLOGY INSTALLATION MANUAL www acornfirese...

Page 2: ...7 ZONE WIRING 12 7 1 Specific device wiring instructions 13 7 1 1 CP3 AD Manual Call Point 13 13 7 1 2 MKII detectors All types Base connection 13 7 1 3 ZAI MI Input Module 14 7 1 4 ZAIO MI Input out...

Page 3: ...3 16 2 Viewing Faults during a fire alarm condition 33 16 3 Viewing Zone Disablements during a fire alarm condition 33 16 4 Viewing Device Disablements during a fire alarm condition 33 16 5 Viewing Zo...

Page 4: ...th point eg building plumbing will help to discharge any static Always hold the PCB by its sides and avoid touching the legs of any components Keep the PCB away from damp dirty areas e g in a small ca...

Page 5: ...10 Test Condition Option with requirements The ID2 also has the following ancillary functions not required by the Standard Serial repeater output RS485 2 2 Power Supply Section The ID2 Fire Alarm Pan...

Page 6: ...ed sounders but also has 2 conventional sounder circuits All sounders on a ID2 panel will activate on any alarm It has been designed to give the advantages of an addressable system with the simplicity...

Page 7: ...step manner the procedure for the basic design and installation of the ID2 range of Fire Alarm Control Panels It gives detailed instructions on how to use all the features on this fire alarm panel For...

Page 8: ...s a bit of thought to zone allocation during the system design stage 1 Decide on the zone allocation for the system Each default zone can have a maximum of 15 devices fitted Consider the simplified 3...

Page 9: ...g to BS5839 Pt1 2013 Clause 26 Fire Detection and Alarm Systems for Buildings Code of Practice for System Design Installation and Servicing are Standard fire resisting cable to PH30 classification of...

Page 10: ...e that holds the panel manuals If semi flushing or fitting to a tight space remember to remove the manuals before fitting to the wall Fix the enclosure to the wall using the three mounting holes provi...

Page 11: ...el via the cable gland the mains cable should be passed twice through the provided ferrite This is made easier by removing the outer insulation The cable is then connected to the Live Earth and Neutra...

Page 12: ...CALCULATIONS The two batteries are wired in series to give 24 Volts Connect the ve of Battery 1 to the black battery charger lead Connect the ve of Battery 2 to the red battery charger lead The ve of...

Page 13: ...be wired with up to 8 separate radial circuits each with 15 devices per circuit It may also be wired as a single loop When Wired as a Loop Zone 1 is used as Loop OUT Side A and Zone 2 is used as Loop...

Page 14: ...negative out terminal on the call point The following terminals are used for connecting the call point 2 x Negative in terminals note if you only connect to the negative in terminals then the isolator...

Page 15: ...Date 06 04 2016 PAGE 14 Deep Base MKII CB D Common Base MKII CB 7 1 3 ZAI MI Input Module The end of line resistor value is 20K and the trigger resistor value is 1 K 7 1 4 ZAIO MI Input output Module...

Page 16: ...der circuit is 10K When using the ZASC make sure the PSU being used has a fault output relay so that in the event of a power supply fault it is reported to the control panel Note All Power Supplies us...

Page 17: ...It may also be programmed via the handheld programming tool Connecting the sounder is done using the terminals in the back box of the device Please refer to the above diagram 7 1 8 Sandwich Sounder T...

Page 18: ...C Wall Mount MKII ARL W There are two versions of the remote LED Wall mounted and Ceiling mounted The ceiling mounted version requires a standard detector base Each version of the remote LED can moni...

Page 19: ...el translates the address into a zone and ID Each zone starts with ID1 in order to simplify the addressing To assist with setting the dip switches there is a free app available for download on the APP...

Page 20: ...OFF OFF OFF ON OFF ON 2 14 ON OFF OFF OFF OFF ON ON ON 6 14 ON OFF OFF OFF OFF ON OFF ON 2 15 OFF OFF OFF OFF OFF ON ON ON 6 15 OFF OFF OFF OFF OFF ON OFF ON 3 1 OFF ON ON ON ON OFF ON ON 7 1 OFF ON...

Page 21: ...least 5V of superimposed data signal The exact calculation equations are beyond the scope of this manual because of the distributed load of the sounders on the loop but the following table gives a rou...

Page 22: ...O relays to the detector circuits Fault Output FAULT This is a SELV volt free relay that operates in the Fault condition It is Normally Energised which ensures it can give a fault signal even in the e...

Page 23: ...ing the wiring Figure 6 Cable connections All cables entering the enclosure should have cable glands which will prevent unwanted openings in the enclosure The Zone circuits should be connected to the...

Page 24: ...2 repeaters can be powered from the Aux24V DC output on the panel If 3 or more are to be connected then they must be powered from external 24V power supplies The panel supports up to 8 repeaters ID2...

Page 25: ...ws that pressing NEXT button will take you to Engineer Menu 2 4 Press button 1 will bring up the Zone menu Press 1 to view zone contents or press 2 to reconfigure the zones 5 Press 2 to reconfigure th...

Page 26: ...d Select option 1 to set time date Enter the Day Month Year Hour Minutes as prompted and press enter to save or Cancel at any time to exit 12 6 Changing the alarm Tones sounders For most applications...

Page 27: ...signals a MCP alarm when operated Used when device being monitored is Manually triggered and the system is set to distinguish manual automatic alarms P PREALARM I O signals a Pre Alarm when operated...

Page 28: ...ges The panel will have one of 2 language banks English Spanish Portuguese French Italian OR English Hungarian Serbian Lithuanian Other languages are available on request 12 10 Software Versions From...

Page 29: ...w Confirming alarm 3 If the device in alarm has zonal verification set the panel will turn on the sounders of all other detectors set to zonal verification in that zone 4 If the detector drops below t...

Page 30: ...set This brings up the screen to select to reset The panel can be reset as follows Option Item Function 1 Logs Clears event log Note that the Event counter is not reset Code 159 to reset 2 Factory Set...

Page 31: ...n alarm LED Flasher Press 4 Ring sounder Press GENERAL TEST Select alarm verification Press 8 Configure Sandwich Sounder Base Press 7 Disable this device Press General Disable Configure I O OUTPUT Pre...

Page 32: ...This device is signalling an internal fault by returning a value of less than 8 Device Label This is the 20 character description of the device location entered by the installer To change this Press E...

Page 33: ...recorded are Power On Startup Panel Reset Evacuate Access Level 2 Access Level 1 Sounders Silenced Configure Loops Time Date Set Zone Disabled Zone Enabled Device Disabled Device Enabled Zone Test St...

Page 34: ...e LEDs will show general fault information To show fault event details on the LCD screen press the CANCEL button Prev next will now scroll through the faults Press cancel to return to viewing the fire...

Page 35: ...he screen will first prompt for a code 248 The screen will then show ZONE DISABLEMENT ZONE 1 The panel is now in SELECT DISABLEMENT MODE 3 Press NEXT key until the required zone or sounders are DISPLA...

Page 36: ...ED ZONES To view which zones are disabled press 1 and then scroll through all the zones by pressing the Next button If a zone is not disabled the screen will show If a zone is disabled the screen will...

Page 37: ...d Zone Test LEDs will now be lit 7 Detectors in this zone can now be tested with smoke spray The Detector will light it s LED until the smoke clears then it will reset The Sounders the fire relay are...

Page 38: ...lier If the wiring polarity is correct check that there is no cable break on the loop If there is a break the panel will report the break after 60 seconds or so and the break can be verified my measur...

Page 39: ...ine the problem line Note connecting other equipment eg an oscilloscope or a PC to the panel can give an earth fault The Screen will indicate if it is a Positive or Negative voltage shorting to earth...

Page 40: ...unning condition due to various unexpected phenomena This will result in the panel attempting to correct itself Should this fault occur the System Fault LED General Fault LED General Fault relay and f...

Page 41: ...es 20 2 Device Values for Battery calculation Device Quiescent Alarm Comment ID2 Panel 50mA 102mA This is the current used during mains failure ID2 Repeater 50mA 75mA Fyreye MKII Addressable Optical S...

Page 42: ...r panel IQD 4 x 10x0 9 0 6 0 65 1 0 1000 4 x 11 25 1000 0 045 A IAP 0 102A IAD 4 x 10x7 2 2 5 7 3 2 0 1000 4 x 83 8 1000 0 3352 A Therefore using the equation Battery Size Standby time in Amp Hours 1...

Page 43: ...al sounders 11 Fault Relay Volt free relay normally energised Operates on any fault 12 Fire Relay Volt free relay Operates on a fire condition 13 RS485 Connection for Repeater panel 14 15 RS232 NOT AC...

Page 44: ...AT C I E OUTPUT 900 mA IMIN AT C I E OUTPUT 0 4 mA OUTPUT VOLTAGE RIPPLE 700mV MAX CURRENT DRAW BY PSE 2mA MAX BATTERY INTERNAL RESISTANCE RIMAX 1 5 CHARGER VOLTAGE 27 6V 22 24 o C CHARGER CURRENT 300...

Page 45: ...rences to 2013 version 4 occurrences Added loop wiring terminal information Added info to Electrical Spec Max sounders Max loop zone current Aux 28V voltage current Changed number of repeaters that ca...

Reviews: