MKII-xx Installation Guide 

 

32-0067-r03                                                             

  1 / 2 

17/10/2017

 

Zeta Alarms Limited, 72/78 Morfa Road, Swansea, SA1 2EN

 

 

Wiring Diagram 

 

Note: 

Polarity must be observed on detector as indicated on schematic wiring diagram. 

Earth terminal is provided to maintain earth screen continuity. It does not connect to this detector head. 

 

Base Installation 

Connect the zone wires to the appropriate terminal. Tighten with a correct sized screwdriver: a wrong screwdriver 
may damage the screw heads. 
Make sure that the base contacts are clean and unobstructed. 
Note, the base model No. for MKII Series is MKII-CB or MKII-CB/D 

 

Detector Head Installation 

If there is still minor construction work in progress, the head may be fitted, provided that the dust cover is still in 
place. 
To fit the detector, mate the detector onto the base and rotate the detector in a clockwise direction until the 
detector loads into the base. Continue to twist clockwise to secure it. 

 

Model 

There are 5 models of Fyreye II Conventional Detector. 

 
Monitor state 

   

 

 

 

 

 

 

 

 

 

 

In monitor state, the two red LEDs on the top cover will blink every 5 seconds. 
See Fig-1. 

 

Pre-alarm state 

In pre-alarm state, LED pairs will blink a clockwise circle in every 5 seconds. 

 

Fire alarm state

   

 

In fire alarm state, the two LEDs shown in Fig-1 will light. The other 3-pairs of LED will light for 0.5 seconds 
rotating clockwise. 

 

False alarms 

In case of false alarm, the LED pairs will blink alternately. Check if the air around the detector is 
clear. Fan the air around the smoke alarm if necessary, until the alarm turns off. If the false alarm 
occurs frequently or continuously, arrange to have the unit serviced. 

 
Sensitivity Read 

Take the Sensitivity Test Wand making the receive diode against the light-emitting diode (see Fig-2).   
And push the button of the Sensitivity Test Wand, the sensitivity will be displayed on LCD of Wand for a few 
moments later.

 

 

Drift Compensation Limit 

In the case of the smoke chamber reaching the end of it`s compensation limit, the detector will flash it`s LEDs 
continuously to signal that the detector should be replaced. This can be confirmed with the Sensitivity Test Wand.

 

Part No 

Model No. 

Description 

CPR No. 

LPCB No 

80-200 

MKII-OP 

Conventional optical detector 

0832-CPR-F0067 

330n/01 

80-202 

MKII-HR 

Conventional A2R heat detector 

0832-CPR-F0071 

330q/02 

80-204 

MKII-HF 

Conventional A2S heat detector 

0832-CPR-F0073 

330q/01 

80-206 

MKII-OH 

Conventional optical and heat detector 

0832-CPR-F0069 

330p/01 

80-208 

MKII-HF/CS90 

Conventional CS heat detector 

0832

CPR

F1922 

330q/06 

Fig-1 

Fig-2 