PREMIER AD USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Approved Document No: GLT.MAN-106A
PAGE 5
Issue: 2.00
Authorised: GH Date: 16/07/2007
4. PANEL INDICATIONS & CONTROLS
4.1 INDICATIONS
4.2 CONTROLS
The Premier AD has
been designed to be as
straight forward as
possible.
To help achieve this it
has been designed so
that its LEDs are the
primary display.
Every possible fault has
its own unique LED.
Each LED is used to
represent only one
condition.
This helps avoid the
confusion caused when a
single LED is used for 2
or more conditions.
The LCD is used during
setup, and to give
detailed information
about zone faults.
The controls on the Premier AD are grouped together to try to
be as user friendly as possible.
The Silence, Reset & Start/Stop Sounder buttons are the
main control buttons.
Silence = turn off the panels buzzer
Stop/Start = turn off external sounders
Reset = return panel to normal condition.
To silence a panel after an alarm, press Stop/Start, followed
by silence. Record the LCD details in the log book, then press
Reset.
The previous & Next buttons by the LCD are used to scroll
between fault messages. The next button is also used in the
Device Status Menu.
The Test function Confirm, Test & Select buttons are used to
control the one man test mode.
The Disablement Select, Confirm & Disable are used to select
panel section disablements.
The numeric section is for entering access codes, and for
entering device addresses.
The alphabet keys are used to enter device labels in the
programming menu.
The remaining 5 buttons are miscellaneous items, each ones
function is clearly labelled.
IN THE EVENT OF AN ALARM
After the site has been deemed safe for return, to return the panel to normal: -
1. Turn keyswitch to Controls Enabled position.
2. Press
Stop/Start
= turn off external sounders
3. Press
Silence
= turn off the panels buzzer
4. Record the LCD details in the Fire Alarm Log Book
5. Press
Reset
= return panel to normal condition.