Written by:.JBJ
Checked by: RP
Document Number: Premier MX User 1.doc
Page 10 of 19
14/12/06
o
The Fire Protection Fault/Disabled LED will change to the “Off-flash”
indication while the cursor is on it, changing to off if the cursor is
moved on.
o
The general Disablement LED will be cleared if no other disablements
are present.
•
To quit the disable/enable mode:
o
To exit the Select Mode, press the Select On/Off button.
o
The Select On LED will clear.
o
The cursor indication will clear.
o
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
4.6.
To Select/Clear One Man Zone Test.
•
To access test selection mode:
o
Turn the Access Controls Keyswitch on the panel door to position “1”.
o
Press the Select On/Off button to enter the Select Mode:
o
The Select On LED will light.
o
The cursor indication will pulse the yellow Zone 1 fault/disabled/test
LED.
•
To select the zone to be tested:
o
Use the Select
↓
button to move the pulsed cursor indication down
through the fault LEDs until it pulses on the required zone. [The Select
↑
button moves the cursor up].
•
To apply the test mode to the selected zone:
o
Press the Test button to activate the test condition on the selected zone.
o
The zone fault/disabled LED will change to the “On-flash” indication
while the cursor is on it, changing to steady if the cursor is moved on.
o
The general Test LED will light.
•
To clear the test mode on the selected zone:
o
Press the Test button again or press the Enable button to clear the test
condition enabling normal operation of the selected zone.
o
The zone fault/disabled LED will change to the “Off-flash” indication
while the cursor is on it, changing to off if the cursor is moved on.
o
The general Test LED will be cleared if no other circuits are in the test
condition.
•
To quit the zone test selection mode:
o
To exit the Select Mode, press the Select On/Off button.
o
The Select On LED will clear.
o
The cursor indication will clear.
o
Set the Access Controls Keyswitch back to position “0” to lock the
controls.
4.7.
To Select/Clear One Man Sounder Test.
•
To access test selection mode:
o
Turn the Access Controls Keyswitch on the panel door to position “1”.
o
Press the Select On/Off button to enter the Select Mode:
o
The Select On LED will light.
o
The cursor indication will pulse the yellow Zone 1 fault/disabled/test
LED.