Written by:.JBJ
Checked by: RP
Document Number: Premier MX User 1.doc
Page 6 of 19
14/12/06
3.2.
User Controls - [showing optional Clock Module]
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
0
1
C.E.L. No 1800456 - 32 ZONE
FIRE
POWER SUPPLY ON
POWER SUPPLY FAULT
SYSTEM FAULT
GENERAL FAULT
EARTH FAULT
FUSE FAILED
REPEATER FAULT
FAULT ROUTING FAULT/DISABLED
SOUNDER FAULT/DISABLED
SOUNDER TEST
FIRE PROTECTION FAULT/DISABLED
FIRE ROUTING ACTIVE
FIRE ROUTING FAULT/DISABLED
BUZZER
SILENCE
EVACUATE
RESET
ENABLE
DISABLE
TEST
TEST DISPLAY
ALARMS
RESOUND
SELECT
ON/OFF
SELECT
SILENCE/
OVERRIDE
ON/OFF/
DELAY
ZONE LOCATION
ZONE LOCATION
FIRE
1. THE RED ZONE INDICATOR
WILL PULSE SHOWING THE
LOCATION OF THE FIRE.
2. CARRY OUT THE
REQUIRED FIRE DRILL.
3. TO SILENCE ALARMS
PRESS SILENCE ALARMS.
4. TO RESET FROM THE FIRE
CONDITION PRESS RESET.
FAULT
1. DETERMINE THE CAUSE
OF THE FAULT.
2. PRESS SILENCE BUZZER.
3. CALL YOUR SERVICE
ENGINEER.
SYSTEM FAULT
THE PANEL IS INOPERATIVE.
ARRANGE FOR
ALTERNATIVE FIRE
DETECTION MEASURES.
DISABLEMENT AND TEST
1. PRESS SELECT ON/OFF.
THE LED WILL ILLUMINATE.
2. SELECT THE ZONE OR
OUTPUT USING
↑
AND
↓
. THE
FAULT LED WILL PULSE.
3. PRESS DISABLE OR TEST.
4. TO RE-ENABLE, SELECT
THE ZONE OR OUTPUT AND
PRESS ENABLE.
MODEL:
PRECEPT EN 32
EN54-2: 1997, EN54-4: 1997
C.I.E. PRODUCTION PERIOD: 1
Certificate Number 018c/06
2 1 : 1 8 : 0 5
D / N OF F
Switch Description
Functionality Button
Availability
Evacuate
Operates all sounders continuously and lights the Evacuated LED adjacent the
button until the silence button is operated
When controls are unlocked
Silence/Resound
Alarms
Following a fire alarm condition, 1st operation stops sounders. The General Fire
LED and the Zonal fire LED will change from flashing to steady. 2nd operation
restarts the previously silenced sounders
When controls are unlocked
Reset
Clears the panel display, resets the zones, outputs and operates the reset relay.
When controls are unlocked
and [if silence before reset is configured]
alarms silence switch has been operated.
1] Press to stop the buzzer sounding in fire or fault conditions.
When controls are locked or unlocked
Silence Buzzer
2] In 2 Stage Delay Mode, with stage 1 delay running, press to start stage 2
delay otherwise all delayed outputs operate when Stage 1 timer times out.
When the panel is in the fire condition and
the delay is running. Controls are locked
or unlocked
1] Press once to Enable the delay mode, lighting the adjacent delay on LED.
Press again to disable the delay mode and turn off the LED
1] When controls are unlocked
and delay
period is set to a value > 0.
Delay
On/Off/Override
2] Overrides the delay when delay is running, turning the delay mode and the
LED off. All delayed outputs will operate immediately.
2] When the panel is in the fire condition
and the delay is running.
Select On/Off
Enables the User select feature [ Select
↑
Select
↓
] for selection of zones or
outputs for disablement/re-enablement also Day/Night On/Off selection and
setting current time on Clock Module when fitted.
When controls are unlocked
Test Display
Press to illuminate all LEDs on the display and operate the buzzer. All
indications remain active for approx 5 seconds after button release. Also
displays alarm count on Clock Module [when fitted]
When controls are locked or unlocked
Enable
Press to clear the disablement or test condition on a zone or output selected via
the User Select feature.
When controls are unlocked, the Select
switch has been operated and a zone or
output has been selected.
Disable
Press to disable a zone or output selected via the User Select feature.
As above.
Test
Press to initiate the One Man Test on sounders or zones as selected via the User
Select feature.
As above.
Select
↑
Select
↓
Used to scroll the cursor indication through the zone and output fault LEDs on
the display to select a zone or output for disablement, or test. [LED illuminated
when Select Mode is active]. Also scrolls through Clock Module menu [when
fitted].
When controls are unlocked and the Select
switch has been operated.
Access Controls Keyswitch:
0 – Controls Locked
1 – Controls Unlocked