background image

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 
 
 
USER MANUAL ,  
MAINTENANCE GUIDE  
& LOG BOOK

 

Simplicity Plus

 
64 OR 126 DEVICE CAPACITY,  
SINGLE LOOP ANALOGUE ADDRESABLE FIRE ALARM CONTROL PANEL 

Summary of Contents for SP-64

Page 1: ...USER MANUAL MAINTENANCE GUIDE LOG BOOK Simplicity Plus 64 OR 126 DEVICE CAPACITY SINGLE LOOP ANALOGUE ADDRESABLE FIRE ALARM CONTROL PANEL...

Page 2: ...A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL 7 6 THE FAULT CONDITION 8 6 1 DIFFERENT TYPES O...

Page 3: ...e fire brigade To reset the panel press the reset button If the panel goes back into alarm silence the sounders and call the engineer What to do if the Fire Alarm Panel shows a Fault Yellow LED Write...

Page 4: ...y evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point Splits the building into Zones each covering a different area of the building...

Page 5: ...y Call point elements held on site 47 2 j 1 2 11 In the event of a prealarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenan...

Page 6: ...ly as possible The Silence Reset Start Stop Sounder buttons are the main control buttons The previous Next buttons by the LCD are used to scroll between fault messages The next button is also used in...

Page 7: ...ssages for each device or reconfigure the panel Select Covered to exit the menu iv TEST MODE SELECTION FOR TEST ENGINEER ONLY This access level is obtained by pressing the test button and entering the...

Page 8: ...tion momentarily pressing the Start Stop will cause the Alarm sounders to sound Pressing the Start Stop button again will Silence the Alarm Sounders Note If the Alarm Sounders have been disabled press...

Page 9: ...s there is a problem with the mains supply or one of its fuses Low Battery indicates that the battery voltage has dropped below 21 volts and that these batteries are no longer working If the mains sup...

Page 10: ...curs the responsible person should Turn keyswitch to Controls enabled and press silence flt tone button to silence the fault buzzer Write down the fault s in the Log Book at the back of this Manual Ta...

Page 11: ...der needs to be disabled then press DISABLEMENT SELECT again until the required zone or sounder is selected 5 If the panel needs to be taken out of SELECT DISABLEMENT MODE eg to silence a fault on ano...

Page 12: ...A OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User needs to know a...

Page 13: ...4 97 7 14 1 56 4 98 7 15 1 57 4 99 7 16 1 58 4 100 7 17 2 59 4 101 7 18 2 60 4 102 7 19 2 61 4 103 7 20 2 62 4 104 7 21 2 63 4 105 7 22 2 64 4 106 7 23 2 65 5 107 7 24 2 66 5 108 7 25 2 67 5 109 7 26...

Page 14: ...ing work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that...

Page 15: ...INTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 108 PAGE 14 Issue 2 00 Authorised GH Date 04 06 2007 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITI...

Page 16: ...t No GLT MAN 108 PAGE 15 Issue 2 00 Authorised GH Date 04 06 2007 FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN...

Page 17: ...roved Document No GLT MAN 108 PAGE 16 Issue 2 00 Authorised GH Date 04 06 2007 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CA...

Page 18: ...all points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for complia...

Page 19: ...mmendations of section 2 of BS 5839 1 2002 for the system category described below except for the variations if any stated in this certificate Name in block letters Position Signature Date For and on...

Page 20: ...een provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be und...

Page 21: ...in this certificate Name in block letters Position Signature Date For and on behalf of Address Postcode The extent of liability of the signatory is limited to the system described below Extent of the...

Page 22: ...e Simplicity Plus Fire Alarm System installed at Address Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accor...

Page 23: ...arm System installed at Address The following work is required before the system can be accepted All installation work appears to be satisfactory The system is capable of giving a fire alarm signal Th...