MZX Fire detection system

The 602SB Sounder Base may be used with or 
without an associated detector.  When used 
with an associated detector, removal of any 
detector or loss of power to the detection circuit 
may cause the sounder to cease 
operating.  When used without an associated 
detector, the wiring should be as shown in the 
alternate wiring scheme.  A cap Part No. 
557.001.040.A.T.Y should be fitted in place of a 
detector.

Features

The 602SB Sounder Base provides eight tone 
and variable volume settings.

Wiring Notes

The following notes apply: 

All wiring must conform to the current edition 
of IEE Wiring Regulations and BS 5839 Part 1.

All wiring must be free of earths.

Setting Sounder Output 
Options

The sounder outputs are set as follows:

Tone - using the 4-way DIL switch (Fig. 3 and 
Table 2 refer).

Volume - using the trimmer tool (S/C No. 
517.050.015) (Fig. 3 refers).

 

DIL Switch Settings

1 2 3 4  Response 

Sound 

Marketing
Tone No.

0 0 0 x Dutch

7

Table 2: DIL Switch Settings

0 0 1 x Temporal  4

-

0 1 0 x Slow  Sweep

3

0 1 1 x March Time Beep

25

1 0 0 x Fast  Sweep

2

1 0 1 x Temporal  3

-

1 1 0 x Two  Tone

11

1 1 1 x Continues

14