Installation and Operating Instructions V04 18
5.4 AC connection
5.4.1 Conditions for the AC connection
Cable Requirements
The grid connection is established using three conductors (L, N, and PE).
We recommend the following requirementsforACcable.
Object Description
Value
A
External diameter
9 to 14mm
B
Copper conductor cross-section
4 to 6 mm²
C
Stripping length of the insulated conductors
approx. 12 mm
D
Stripping length of the outer sheath of AC cable
approx. 120mm
The PE conductor must be 10mm longer than the L and N conductors.
Cable design
The cable must be dimensioned in accordance with the local and national directives for
the dimensioning of cables.
The conductor cross-section should be dimensioned to avoid power loss in cables
exceeding 1% of rated output power.
The higher grid impedance of the AC cable makes the inverter easier to disconnect
from the grid due to excessive voltage at the feed-in point.
Danger to life due to high voltages in the inverter
• Before performing the electrical connection, ensure that the AC circuitbreaker
is switched off and cannot be reactivated.