29 Installation and Operating Instructions V04
5.5.4 Connecting the PV array
1. Ensure that the individualACcircuitbreaker is switched off and ensure it against
reconnection.
2. Ensure that the DC switch is switched off and ensureit against reconnection.
3.Ensure that there is no ground fault in the PV strings.
4. Check whether the DC connector has the correct polarity.
If the DC connector is equipped with a DC cable having the wrong polarity, the DC
connector must be reassembled. The DC cable must always have the same
polarity as the DC connector.
5.Ensure that the open-circuit voltage of the PVstrings does not exceed the
maximum DC input voltage of the inverter.
6.Connect the assembled DC connectors to the inverter until they audibly snap into
place. Ensure that all DC connectors are securely in place.
7. For unused DCconnectors, push down the clamping bracket and push the swivel
nutup to thethread.Insert the sealing plug into the DC connector. Tighten the DC
connector (torque:2.0Nm). Finally insert the DC connectors with sealing plugs into
the corresponding DC inputs on the inverter.
Damage to the inverter due to overvoltage
If the voltage of the strings exceeds the max. DC input voltage of the inverter, it
can be destroyed due to overvoltage. All warranty claims become void.
• Do not connect strings with an open-circuit voltage greater than the maximum
DC input voltage of the inverter.
• Check the design of the PV system.