65 Installation and Operating Instructions V04
Presumable
Fault
36
• Make sure the grounding connection of the inverter is
reliable.
•Make a visual inspection of all PV cables and modules.
If this fault is still shown, contact the service.
37
• Check the open-circuit voltages of the strings and make
sure it is below the maximum DC input voltage of the
inverter.
If the input voltage lies within the permitted range and
the fault still occurs, contact the service.
38
•Check the PV array’s insulation to ground and make sure
that the insulation resistance to ground is greater than 1
MOhm. Otherwise, make a visual inspection of all PV
cables and modules.
• Make sure the grounding connection of the inverter is
reliable.
If this fault occurs often, contact the service.
40
•Check whether the airflow to the heat sink is obstructed.
•Check whether the ambient temperature around the
inverter is too high.
41, 42
43, 44
45
• Disconnect the inverter from the grid and the PV arrays,
reconnect them after 3 minutes.
If this fault is still being shown, contact the service.
Permanent
Fault
1, 2,3,
4,5,6, 8,9
• Disconnect the inverter from the grid and the PV arrays,
reconnect themafter 3 minutes.
If this fault is still being shown, contact the service.
Contact the Zeversolarservice if you meet other problems not in the above table.