SERVICE FIELD TEST UNIT
MM13927 RvD 10/03 Page 2-10
2-3.2
Troll Command (Proportional Solenoid) Testing with Amp Meter
A) Ensure power is removed from both the Processor and the
Clutch Power Supply.
B) Disconnect the Clutch Harness from the number
3
Processor
connector/pigtail.
C) Insert the Break-out Box between the number
3
Processor con-
nector/pigtail and the Clutch Harness as shown in Figure 2-
D) Set up the Multimeter to measure (mA.) and connect the black
lead to black socket and the red lead to the red socket labeled
“TROLL COMMAND” as shown in Figure 2-13:.
E) Turn power ‘On’ to the Processor and the Clutch Power Sup-
ply and take command at a Remote Station with the Control
Head lever in the Neutral/Idle position.
F) Depress the Transfer Button again for approximately 2 sec-
onds until the red LED on the Control Head begins blinking at
a fast rate (Troll Mode Indication).
G) Flip switch away from "Troll Command" to read current
through meter.
H) Move the Control Head lever to the Ahead detent. The cur-
rent measurement should be the correct value for minimum
clutch pressure (shaft rotations). This value varies depending
on the type of Marine Gear. Refer to the Literature provided
with the Trolling Valve and the Processor for specifics.
I) Slowly advance the Control Head lever while monitoring the
current. The current should increase or decrease, depending
on the Gear type, in proportion with the Control Head lever
movement. Once again, refer to the Literature provided with
the Trolling Valve and the Processor for specific values.
J) Continue to move the Control Head lever forward until the
red LED stops blinking (lit steady). The current should drop to
0 mA.
Figure 2-13: Troll Connection (Proportional Solenoid with Amp Meter)
Summary of Contents for ClearCommand 9000 Series
Page 132: ......
Page 133: ...APPENDIX A...
Page 134: ......
Page 139: ......
Page 140: ...Page A 4...
Page 143: ......
Page 144: ...10...
Page 148: ...Page A 18...
Page 149: ...Page A 19 TEMPLATE...
Page 150: ...Page A 20...
Page 152: ...Page A 22...
Page 154: ...Page A 24...
Page 156: ...Page A 26...
Page 157: ...Page A 27 Drawing 11488D 1 Twin Screw Single APS Connection Alternate Remote Switch...
Page 158: ...Page A 28...
Page 159: ...Page A 29 Drawing 11488D 2 Twin Screw Dual APS Connections...
Page 160: ...Page A 30...
Page 161: ...Page A 31 Drawing 11488D 3 APS Notes Page...
Page 162: ...Page A 32...
Page 164: ...Page A 34...
Page 166: ...Page A 36...
Page 170: ...Page A 40...
Page 172: ...Page A 42...
Page 176: ...Page A 46...
Page 178: ...Page C 48 ZF Mathers LLC 12125 Harbour Reach Drive Suite B Mukilteo WA 98275...
Page 179: ...APPENDIX B...
Page 180: ......
Page 234: ...Appendix B 6...
Page 238: ...Appendix B 10...
Page 242: ...Appendix B 14...
Page 247: ...Service Field Test Unit Reference Manual MM13927 Rev E 4 07...
Page 248: ......
Page 250: ...Page ii Table of Contents...
Page 264: ...SERVICE FIELD TEST UNIT MM13927 RvD 10 03 Page 3 2...
Page 265: ...APPENDIX C...
Page 266: ......
Page 267: ...Appendix C 1 Drawing 12284A 1 ClearCommand Diagram all options...
Page 268: ...Appendix C 2...
Page 269: ...Appendix C 3 Drawing 12284A 2 ClearCommand Circuit Board Connections...
Page 270: ...Appendix C 4...
Page 271: ...Appendix C 5 Drawing 12284A 3 ClearCommand Drawing Notes Page...
Page 272: ...Appendix C 6...