SET UP
Page5-11
5-6.2.1.2 Function Code E6 – High Idle
5-6.2.1.3 Function Code E1 – Throttle in Neutral
This Function allows the engine RPM at Neutral to be
adjusted independently of the RPM at Idle Ahead
and Astern.
The available Values for this Function are 00.0 to
25.0 percent of the Throttle Range.
The Default Value is 00.0%.
5-6.2.1.4 Function Code E4
– Throttle Maximum Astern
Figure 5-16: Display LED Function E5 Set Up
Activated
To change the Value (Refer to Sections 5-2 and 5-3,
page 5-5):
A) Scroll to Function Code E5.
B) Activate Set Up Mode.
C) Scroll Up or Down to the desired Value.
D) Store the Value to memory.
This Function Code Programs the RPM of the sec-
ond, elevated Idle.
The available Values for this Function are
00.0
to
20.0
% of Throttle Maximum.
The Default Value is
00.0
%.
The Value selected is a percentage of the Value
selected in Function Code
E3
– Throttle Maximum.
NOTE: T
HIS
F
UNCTION
IS
TYPICALLY
PROGRAMMED
DURING
D
OCK
T
RIALS
OR
S
EA
T
RIALS
. R
EFER
TO
S
ECTION
6-5,
PAGE
6-2.
Figure 5-17: Display LED Function E6 Set Up
Activated
To change the Value (Refer to Sections 5-2 and 5-3,
page 5-5):
A) Scroll to Function Code
E6
.
B) Activate Set Up Mode.
C) Scroll Up or Down to the desired Value.
D) Store the Value to memory.
Figure 5-18: Display LED Function E1 Set Up
Activated
To change the Value (Refer to Sections 5-2 and 5-3,
page 5-5):
A) Scroll to Function Code
E1
.
B) Activate Set Up Mode.
C) Scroll Up or Down to the desired Value.
D) Store the Value to memory.
This Function limits the amount of Throttle permitted
in Astern.
The available Values for this Function are
00.0
% to
100.0
%.
The Default Value is
100.0
% of Throttle Maximum.
The Value selected is a percentage of the Value
selected in Function Code
E3
– Throttle Maximum.
Function Code is Blinking
Function Code is Blinking
Summary of Contents for ClearCommand 9000 Series
Page 132: ......
Page 133: ...APPENDIX A...
Page 134: ......
Page 139: ......
Page 140: ...Page A 4...
Page 143: ......
Page 144: ...10...
Page 148: ...Page A 18...
Page 149: ...Page A 19 TEMPLATE...
Page 150: ...Page A 20...
Page 152: ...Page A 22...
Page 154: ...Page A 24...
Page 156: ...Page A 26...
Page 157: ...Page A 27 Drawing 11488D 1 Twin Screw Single APS Connection Alternate Remote Switch...
Page 158: ...Page A 28...
Page 159: ...Page A 29 Drawing 11488D 2 Twin Screw Dual APS Connections...
Page 160: ...Page A 30...
Page 161: ...Page A 31 Drawing 11488D 3 APS Notes Page...
Page 162: ...Page A 32...
Page 164: ...Page A 34...
Page 166: ...Page A 36...
Page 170: ...Page A 40...
Page 172: ...Page A 42...
Page 176: ...Page A 46...
Page 178: ...Page C 48 ZF Mathers LLC 12125 Harbour Reach Drive Suite B Mukilteo WA 98275...
Page 179: ...APPENDIX B...
Page 180: ......
Page 234: ...Appendix B 6...
Page 238: ...Appendix B 10...
Page 242: ...Appendix B 14...
Page 247: ...Service Field Test Unit Reference Manual MM13927 Rev E 4 07...
Page 248: ......
Page 250: ...Page ii Table of Contents...
Page 264: ...SERVICE FIELD TEST UNIT MM13927 RvD 10 03 Page 3 2...
Page 265: ...APPENDIX C...
Page 266: ......
Page 267: ...Appendix C 1 Drawing 12284A 1 ClearCommand Diagram all options...
Page 268: ...Appendix C 2...
Page 269: ...Appendix C 3 Drawing 12284A 2 ClearCommand Circuit Board Connections...
Page 270: ...Appendix C 4...
Page 271: ...Appendix C 5 Drawing 12284A 3 ClearCommand Drawing Notes Page...
Page 272: ...Appendix C 6...