Fig. 4-32 Settings/Advanced Settings/System Setting (3) submenu
o
Basic Unit Numb: power module number for actual configuration, if setting number no the same to
actual number, UPS will alarm.
o
Cabinet Power: cabinet power range, the same power range of bypass.
o
Sleep Mode: when load less than the software setting value, same power module will turn to standby
mode and if the load more than the setting value some power module will turn to inverter mode after
setting the sleep mode enable. Default value is disable.
Fig. 4-33 Settings/Advanced Settings/System Setting (4) submenu
o
Paralallel ID: Parallel operation ID, must modify the ID after set work mode to parallel mode. The
value can be 1~6, default value is 1.
o
Cabinet Paral Basic Units: Parallel cabinet number, must modify the total parallel cabinet number
after set work mode to parallel mode. The value can be 2~6, default value is 2.
o
Cabinet Paral Redunt Units: Parallel redundancy cabinet number, can modify the redundancy
cabinet number after set work mode to parallel mode. The value can be 0~5, default value is 0.