ZGR SCALABLE 60
– 300 KVA
Manual de operaciones
www.zigor.com
32
Fig. 4-34 Settings/Advanced Settings/System Setting (5) submenu
o
Output Freq: Output frequency. The value can be 50Hz or 60Hz.
o
Output Volt Level: Output voltage level. The value can be 220V, 230V, 240V.
o
Inverter Volt Adjust: Inverter voltage adjust. The value can be -5%~0~+5%, step is 0.5%, default
value: 0.
Fig. 4-35 Settings/Advanced Settings/System Setting (5) submenu
o
Battery Group: Must modify the number to actual configuration. The value can be 1~8, default value
is 1.
o
Battery number: Must modify the number to actual configuration. The value can be 30~50, default
value is 32.
o
Single Battery Capability: Must modify the value to actual configuration, the value can be 7~2000.
o
Boost/Float conversion: boost charge and float charge alternate time, the value can be 0~20.