Fig. 4-36 Settings/Advanced Settings/System Setting (6) submenu
o
Chg.cur.limiting coef.: The charging current limit is a multiple of the battery capacity. The value can
be 0.05 0.15, and is 0.1 by default.
o
Cell float voltage: The float voltage value can be 2.23-2.30 V/cell, and is 2.25 V/cell by default.
o
Cell boost voltage: The battery equalized voltage value can be 2.30 2.40 V/cell, and is 2.30 V/cell by
default.
o
Aver charging Duration: boost charge time limit, the value can be 1 999min, and is 240 by default.
Fig. 4-37 Settings/Advanced Settings/System Setting (7) submenu
o
EOD Battery Volt: End of discharge voltage. The value can be 1,60 ~ 1,90, and is 1,80 by default.
o
Float Temp Compen Coeff: modify the voltage of compensation after enable the switch. the value
can be 0,001 ~ 0,007/cell, and is 0,003 by default.
o
Boost Charge Setting: Boost charge disable or enable, and is enabled by default.
o
No Battery Warning: can be no warning when no batter after set disable, and is enabled by default.