Manual de operaciones
www.zigor.com
37
Fig. 4-44 Settings/Advanced Settings/System Setting (12) submenu
o
OUT01~OUT06: Output dry contact port, modify on the LCD, the default value is Disable. The output
port can set to normally closed or normally opened. The default value is normally opened.
Setting value:
No
ITEM
No
ITEM
1
URGENT_ALARM
7
BYPASS_SUPPLY
2
MINOR_ALARM
8
BATTERY_SUPPLY
3
MAIN ABNORMAL
9
NO_SUPPLY
4
BATTERY_LOW_VOLT
10
ECO_MODE
5
BATTERY_SELFCHECK
11
MAINT_CLOSE
6
MAIN_SUPPLY
12
OIL_MACHINE_CONTROL
Table 4-1Valor de ajuste de los contactos libres de potencial
Fig. 4-45 Settings/Advanced Settings/System Setting (13) submenu