Manual de operaciones
www.zigor.com
45
53
0D2
Bypass Fan Fault
Beep continuously
Fault LED lit
Table 4-2 Faults list
Alarm Information
NO
ALARM
CODE
UPS ALARM WARNING
BUZZER
LED
1
103
Battery Over Voltage
Once per second
Alarm LED lit
2
104
BAT Low Pre-warning
Once per second
Alarm LED lit
3
105
Battery Reverse
Twice per second
Alarm LED lit
4
106
Battery EOD
Once per second
Alarm LED lit
5
107
Battery Voltage low
Once per second
Alarm LED lit
6
108
No Battery
Once per second
Alarm LED lit
7
109
Input Phase Reverse
Once per second
Alarm LED lit
8
10A
Input N-Line lost
Twice per second
Alarm LED lit
9
10B
Mains Freq. Abnormal
Once per 2 seconds
Alarm LED lit
10
10C
Mains Volt. Abnormal
Once per 2 seconds
Alarm LED lit
11
10D
REC Comm. Error
Once per 2 seconds
Alarm LED lit
12
10E
Mains input lost
Once per 2 seconds
Alarm LED lit
13
10F
Set Data Err.
Once per 2 seconds
Alarm LED lit
14
121
INV Par. cable abnormal
Once per 2 seconds
Alarm LED lit
15
125
INV Overload
Once per 2 seconds
Alarm LED lit
16
126
INV not synchronized
Beep continuously
Alarm LED lit
17
12A
INV Set Data Err
Once per 2 seconds
Alarm LED lit
18
129
INV Comm. Error
Once per 2 seconds
Alarm LED lit
19
141
Bypass Switch to Num
Once per 2 seconds
Alarm LED lit
20
142
Unit quantity mismatch
Once per 2 seconds
Alarm LED lit
21
143
Parallel Overload
Once per 2 seconds
Alarm LED lit
22
144
Bypass Overload
Once per 2 seconds
Alarm LED lit
23
145
Maint. Switch Misuse
Once per 2 seconds
Alarm LED lit
24
146
ECU Comm. Error
Once per 2 seconds
Alarm LED lit
25
147
Par. cable abnormal
Once per 2 seconds
Alarm LED lit
26
14B
ECU Par. Cable abnormal
Once per 2 seconds
Alarm LED lit
27
14C
ECU Abnormal
Once per 2 seconds
Alarm LED lit
28
14E
BPS Phase Reversed
Once per second
Alarm LED lit
29
162
Once per second
Alarm LED lit
30
14F
BPS Unable To Trace
Once per 2 seconds
Alarm LED lit