Manual de operaciones
www.zigor.com
63
10
Buzzer beeps every 0,5
seconds and LCD
Overload
Remove some load
11
Buzzer long beeps,
The UPS output is in short
circuit
Make sure the load is not in short circuit, and
then restart the UPS.
12
The LED of the Module
with RED light
The module is not inserted
properly.
Pull out the module and insert properly.
13
The UPS only works on
bypass mode
The UPS is set to ECO mode,
or the transfer times to
bypass mode are
limited.
Set the UPS working mode to Single Module
type(non-parallel) or to reset the times of
transferring to bypass or re-start the UPS
14
Cannot Black start
Battery switch is not properly
closed;
Battery fuse is not open; Or
Battery low
Close the battery switch; Change the fuse;
Recharge the battery
15
Buzzer beeps
continuously and LCD
indicates Rectifier fault
or output fault
UPS is out of order
Consult with your local agent for repair
Table 7-1 Trouble shooting
Given the complexity of the equipment, when a serious error occurs and causes the equipment to stop, ZIGOR
customer service should be contacted to assist you step-by-step to your resolution by providing the information
requested.
Para información más detallada:
7.2 Recommended spare parts
You can ask ZIGOR for a list of recommended spare parts for the client systems so that a large percentage of
malfunctions can be quickly and simply repaired.