MAINTENANCE
You can ask for an offer to ZIGOR in order to perform a basic maintenance of this equipment, so that it can
prolong the life of the system.
In order to guarantee the correct operation of the ZGR SCALABLE 60 300 KVA, it is necessary to carry out a
number of maintenance tasks. These tasks enable resolving defects before breakdowns occur and to ensure
correct operation of active and passive safety devices.
The frequency of maintenance tasks is dependent upon the location and the atmospheric conditions. The air
quality (temperature, dust in suspension, etc.) has a great influence on the amount of maintenance work to be
done in order to maintain the functionalities of the equipment within an acceptable level of uncertainty. That is, for
example, if the air contains a great amount of dust in suspension, the maintenance work must be carried out more
frequently than the standard frequency indicated. The recommended maintenance tasks in accordance with
frequency are as follows:
•
Monthly:
o
Visual control of correct operation:
▪
Values within margins.
▪
No active event.
o
Control of the event history, in search of sporadic or repetitive failures.
o
Check nothing blocks the ventilation of the front, rear and side panel and the case bottom.
•
6 monthly:
o
Check on the correct ventilation of the location.
o
Cleaning of the equipment's air inlet filters.
o
Removal of foreign bodies both in the air inlet and outlet.
o
Visual verification of the status of connecting wires, rusting, damage to insulation, etc.
•
Annually:
o
Cleaning and blowing of electronics.
o
Checking the tightening and condition of the cables, power and signal.
▪
Visual checking.
▪
Retightening of the connections.
o
Check for colour changes or deformations due to hot spots.
o
Review of hardware (tightening) and wiring (possible rodent involvement or similar).
o
Cleaning control and water filtration of the room where the system is located.
o
Connection of the external AC protections of the equipment (switches, thermal magnets, etc.) and
complete controlled start of the equipment.
For some of these maintenance tasks, shutdowns and disconnections must be made.
•
Fan: Continual working time of fan is 20000 to 40000 hours. It will be shorter as temperature raises.
Please check the fan periodically, make sure there is wind blowing out from it.
•
UPS status checking:
o
Check to see if there is any fault occurred, fault indictor is on or any alarm there.
o
Please find the cause if the UPS is working in bypass mode.
o
If the UPS is working in battery mode, make sure it is normal; on the contrary, please find out the root
cause, such as Utility Failure or self-check of battery.
WARNING
Incorrect maintenance can render the warranty null and void.