Manual de operaciones
www.zigor.com
67
Output frequency
Line Mode:±1 % / ± 2 % / ± 4 % / ± 5 % of the rated frequency(optional)
Battery Mode: 50 / 60 ± 0,1 % Hz
Crest factor
3:1
Efficiency
95,8 %
BATTERY
Battery voltage
Optional Voltage:
±180 V/±192 V/±204 V/±216 V/±228 V/±240/±252/±264/±276/±288/±300 Vdc
(30/32/34/36/38/40/42/44/46/48/50 pcs optional)
360 Vdc ~ 600 Vdc (30 ~ 50 pcs, 36 pcs define, 36~50 pcs no power derating;
32~34 pcs output power factor 0.9; 30 pcs output power factor 0,8)
Power module Charge Current
18 A (Max.)
UPS cabinet Max. Charge Current
54 A
90 A / 72 A
180 A / 162 A
COMMUNICATIONS
Monitorization
LCD + Software
Communications
CAN, RS485, Parallel, Dry contact port, Relay card(optional), SNMP Card
(optional), Battery temperature sensor (optional)
Alarm
Line Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Audible & Visual alarms
Line Failure, Battery Low, Overload, System Fault
OTHERS
Protections
Short circuit, overload, overtemperature, battery low, fan fault
Transfer time
Utility to Battery
0 ms
Utility to bypass
0 ms
Overload
Line Mode
110% overload for 60 min; 125% overload for 10 min; 150% overload for 1 min
Bypass Mode
135% overload for long term; >1000% overload for 100 ms
Overheat
Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Low battery voltage
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
EPO (optional)
Shut down UPS immediately
MECHANICAL AND ENVIRONMENTAL CHARACTERISTICS
Noise level
< 58 dB
< 61 dB
< 68 dB
Operating temperature
0 ºC
–
40 ºC
Storage temperature
-25 ºC
–
55 ºC (without battery)
Humidity range
0 - 95 % (without condensation)
Altitude
< 1500 m. When > 1500 m, lower the rated power for use
Dimensions
(AnxAlxF)
UPS cabinet
600 x 1200 x 850 mm
600 x 2000 x 850 mm
Module
440 x 86 (2U) x 620 mm
Approx. weigth
UPS cabinet
142 kg
153 kg
295 kg
Module
10 kVA: 19
15 - 30 kVA: 21
STANDARDS
Marks
CE
Directives
EN 60950-1, EN 62040-1:2008/A1:2013, IEC 62040-2:2016, IEC 62040-3:2011,
ROHS
The technical specifications may be modified without prior notice.
ZIGOR