In this operation mode, control panel shows the current status as below:
Fig. 4-6 Control panel in ECO mode
4.2.6
Frequency converter mode
When input frequency is within 40 Hz to 70 Hz, the UPS can be set at a constant output frequency, 50 Hz or 60
Hz. This mode is configurable in setting menu. The UPS will still charge battery under this mode, but bypass is
disabled.
In this operation mode, control panel shows the current status as below:
Fig. 4-7 Control panel in frequency converter mode
Operation procedures
4.3.1
Before Start-up
•
Check that all the loads are off.
•
Check that load connected to the UPS does not exceed the nominal value. It is not recommended to
connect high-consumption devices or with high start-up spikes such as laser printers or motors to the
UPS.
•
Check the installation and load cables to ensure that there are no short-circuits or non insulated parts
within reach of the user.
•
Check that the outlet to which the UPS is to be connected complies with the power requirements and that
it is in good condition.
•
When installing the equipment, it should have ensured that the sum of the leakage current of the UPS and
the connected devices does not exceed 30mA.
•
It is recommended to put the critical loads in SEGMENT2 outlets and the non-essential loads in
SEGMENT1 outlets.
4.3.2
First Start-up
Once the steps outlined in the previous section have been completed, you can start up the unit for the first time.