14.2.1
Connection suggestion for several motors with motor protection unit type STDT
•
Total motor protection: Automatic cut-off by thermocontact actuation motor overtemperature. Button for
Reset after malfunction.
•
Line protection: A thermal over current sensor and a magnetic short circuit releasing elements are the
parts of the integral line protection. Adjustment to the thermal overcurrent sensor to the max. permissible
current of the connected cable (max. line fuse 80 A).
•
No cut-off if the mains supply is interrupted
Fcontrol
FXDM22
U
P
E
V
W
N
L1
L2
L3
L3
N
L2
L1
PE
3~208V...480V
>
1
0
m
m
²
/
2
x
4 mm²
max. 25 A
KT00005N
07.08.2007
1
3
2
4
6
I >
5
STDT16
TB
TB
I >
I >
3~ Motor
3~ 400 V / 7 A
M
3~
PE
V
W
U
TB
TB
4 mm²
1,5 mm²
1
3
2
4
6
I >
5
STDT16
TB
TB
I >
I >
3~ Motor
3~ 400 V / 7 A
M
3~
PE
V
W
U
TB
TB
4 mm²
1,5 mm²
1
3
2
4
6
I >
5
STDT16
TB
TB
I >
I >
3~ Motor
3~ 400 V / 7 A
M
3~
PE
V
W
U
TB
TB
4 mm²
1,5 mm²
14.2.2
Connection suggestion for Bypass with necessary time delay
* Programming function enable (ON / OFF) necessary
Operating Instructions
Fcontrol
–
model series FXDM
Enclosure
L-BAL-E072-GB 1642 Index 008
Part.-No.
101/105