7.2
Select operation mode
Information
Simple installation is possible through the selection of the preprogrammed mode of operation.
This determines the basic function of the device; factory setting
1.01
= Speed controller (activation via
0 - 10 V signal). The controller con
fi
guration is automatically carried out during selection of the
application related mode of operation. The factory presets in accordance with the mode of operation
are based on many years of experience, which is suitable for many applications. Under special
circumstances, these can be individually adapted (see Controller Setup:
“
Controller Con
fi
guration
”
).
The purpose of the device is to reach and maintain the target values set. To accomplish this, the
measured actual value (sensor value) is compared with the adjusted target value, and the controlled
value (modulation) is deduced from this.
Mode
Signal or Sensor
(input)
Function
1.01
Signal 0 - 10 V (PWM)
Speed controller, two step operation wih external switch over (factory setting)
1.02
-
Manual speed controller with direct setting by the
▼
+
▲
keys (0 - 100 % or in 1 -
5 steps)
2.01
Sensor TF..(E1)
Temperature control airconditioning and refrigeration.
(preset set-point 20.0
°
C, P-band 5.0 K)
2.02
Sensor TF..(E2)
Temperature control depending on outdoor temperature
(preset set-point 5.0
°
C, - P-band 20.0 K)
2.03
Sensor TF..(E1)
Temperature control with additional functions (shutter and heating)
2.04
1x Sensor TF..(E1)
1x Sensor TF..(E2)
Temperature control with two sensors, comparison or average
2.05
1x Sensor TF..(E1)
1x Sensor TF..(E2)
Temperature control with two sensors differential temperature
3.01
Sensor MBG.. (E1)
Pressure control condensers (refrigeration)
3.02
Sensor MBG..(E1)
Pressure control for condensers with input for refrigerant
3.03
1x Sensor MBG..(E1)
1x Sensor MBG..(E2)
Pressure control for two circuit condensers
3.04
1x Sensor MBG..(E1)
1x Sensor MBG..(E2)
Pressure control for two circuit condensers with input for refrigerant
4.01
Sensor DSG..(E1)
Pressure control for ventilation systems
4.02
1x Sensor DSG..(E1)
1x Sensor TF..(E2)
Pressure control depending on outdoor temperature
4.03
1x Sensor DSG..(E1)
1x BUS RS 485
Pressure control with outdoor temperature-dependent setpoint adaptation and
activation by MODBUS
5.01
Sensor DSG..(E1)
Volume control (constant) for ventilation systems
5.02
1x Sensor DSG..(E1)
1x Sensor TF..(E2)
Volume control with setpoint depending on outdoor temperature
6.01
Sensor MAL..(E1)
Air velocity control e.g. clean room
Operating Instructions
Fcontrol
–
model series FXDM
Base setup
L-BAL-E072-GB 1642 Index 008
Part.-No.
27/105