Additional menu item for mode
4.02
and
4.03
with outside-temperature dependent target-
setpoint.
Outside-temperature dependent target-setpoint
AT
P-min.
-15 °C
T-min.
30 °C
T-Start
S1
18.09.2014
v_pressure_set_dep_outtemp.vsd
[Pa]
S2
T-Band
S1
Setpoint1
S2
Setpoint 2
P-Min SA
Minimum pressure
T-min
Minimum temperature
T-Start
Setpoint reducing will start below this outside temperature
AT
Outdoor temperature
An outside temperature compensation can be
activated (sensor connection
“
E2
”
=
“
Analog In
2
”
) when being operated as a pressure regula-
tion device.
An optimal building climate, e.g., can be
achieved through this. Through this function,
the set and active
“
Setpoint 1
”
or
“
Setpoint 2
”
is
automatically changed proportional to the
measured outside temperature (
Info:
“
Set-
point control
”
).
T-Band SA
T-Band SA
Temperature range in which the setpoint change continiously with outside temperature
T-Start SA
T-Start SA
Setpoint reducing will start below this outside temperature
P-Min SA
P-Min SA
Minimum pressure for very low outside temperature
9.5
Volume control
5.01
...
5.02
9.5.1
Basic setting
5.01
and
5.02
Setting
Base setup
Base setup
Mode
Mode selection e.g.
5.01
E1 Analog In
E1 Analog In
In all group operating modes 5 (
5.01
and
5.02
)
“
E1 Analog In
”
factory setting
“
DSG200.
”
Selection sensor measuring range:
“
DSG 50
”
, *
“
DSG100
”
,
“
DSG200
”
, *
“
DSG300
”
,
“
DSG500
”
,
“
DSG1000
”
,
“
DSG2000
”
,
“
DSG4000
”
,
“
DSG6000
”
(* no standard type).
For sensors with 0 - 20 mA or 4 - 20 mA signal (
jumper for input signal), select
measuring range
“
DSG50
”
...
“
DSG6000
”
.
K-Factor
K Factor
Input of the
“
K factor
”
dependent on the fan (inlet duct).
setting range: 0...7.000
Factory setting: 75
Operating Instructions
Fcontrol
–
model series FXDM
Programming
L-BAL-E072-GB 1642 Index 008
Part.-No.
47/105