KD
D-component
More
“
D-component
”
causes more stability by a clean actual value signal with shorter
correction times
By a actual value signal with a superposition should be done to attitude without
“
D-
component
”
→
0 %
Setting range: 0 - 200 %
value smaller = less
“
D-component
”
value higher = more
“
D-component
”
TI
Integration time = correction time
Setting range: 0 - 200 %
smaller = faster
bigger = more slowly
9.9.10
MODBUS communication watchdog
The MODBUS communication watchdog de
fi
nes the behaviour in case of a communication fault.
Watchdog Mode
Watchdog Mode
Watchdog Mode:
0: no function (Default) = OFF
1: Fault (K1 Function, h58)
2: Watchdog Speed (Frequency)
3: Fault +
fi
xed speed 1 in the case of a communication fault (after watchdog time)
Watchdog Time
Watchdog Time
If the device receives no message in the time window, a de
fi
nable function is executed.
Watchdog time in seconds.
Setting range: 0 - 255 sec.
Factory setting: 0 sec. = off
Watchdog Speed
Watchdog Speed
Setting Watchdog Frequency
Setting range: 0 - Max. Speed
Factory setting: 50 Hz = off
9.9.11
Data on the total control deviation
The total control deviation is comprised of the sum of the control deviations for performance quantities
and work quantities combined and refers to the speci
fi
ed areas.
In direct reference to the acquired input and controlled variables, the maximum deviation to the target
value is <
±
5 %. By activating the menu-assisted adjustment, the total control deviation can be
reduced to a value of <
±
1 %.
For indirect reference of the acquired input value to the controlled variable, i.e., two physical variables
still need to be converted, the deviation can be reduced to <
±
5 % through adjustment.
In the case of an internal default value through the integrated or external terminal, the control deviation
remains at <
±
0.5%.
Operating Instructions
Fcontrol
–
model series FXDM
Programming
L-BAL-E072-GB 1642 Index 008
Part.-No.
59/105