Function
Description Function E2
2E
External Manual mode
Digital outputs K1..K4
Function
Description function K1, K2 ,K3*, K4*
OFF
No function
Relays remain always de-energized
1K
Operating indication (factory setting for
“
K1
”
, non inverting).
Operation without fault, reports enable
“
OFF
”
2K
Fault indication (factory setting for
“
K2
”
, non inverting).
Energized for operation without fault, for enable
“
OFF
”
not energized. De-energized at line,
motor and controller fault, Sensor fault dependent on programming, external fault at digital
input.
3K
External fault separate with message at digital input (factory setting if terminals bridged)
4K
Limit modulation
Over or falling below modulation
5K
Limit
“
E1
”
When over or falling below limits for input signal
“
E1
”
6K
Limit
“
E2
”
When over or falling below limits for input signal
“
E2
”
8K
Group control (Group 2)
Switching on fans depending on modulation
12K *
Group control (Group 3)
Switching on fans depending on modulation
13K *
Group control (Group 4)
Switching on fans depending on modulation
For modes as controller from
2.01
7K
Setpoint Offset
Deviation between actual value and setpoint to high
For modes as temperature controller with additional functions
2.03
9K
Heating function
Switch ON point: temperature = Se/- Offset
Switch OFF point: Temperature around hysteresis over switch ON point
10K
Cooling function
Switch ON point: temperature = Se/- Offset
Switch OFF point: Temperature around hysteresis below switch ON point
*
Function depending on the version of the software available
Limits GW E1, GW E2
Function
Description function GW E1, GW E2
OFF
no function
1L
Indication with the centralized fault of a programmed relay (IO allocation Function
|
2K
|
).
Warning symbol in display,
“
AL
”
code in events memory.
2L
Is merely displayed in the events menu as message
“
msg
”
.
Operating Instructions
Fcontrol
–
model series FXDM
Menu tables
L-BAL-E072-GB 1642 Index 008
Part.-No.
89/105