PINs
PIN
Function
PIN 0010
Opening service menu, if PIN-protection activated
PIN 1234
Opening
“
setting
”
.
if
“
set protection
”
=
“
ON
”
(
Controller Setup)
PIN 9090
Restore user setting
PIN 9091
Save user setting (corresponds function
“
Save user setup
”
=
“
ON
”
Controller Setup)
PIN 9095
Restore factory setting = delivery status
11
Diagnostics menu
Diagnostic
The diagnostics menu supplies information about the momentary operating condition
of the device.
00056:46:13
O
= Operation,
T
= Time,
C
= Controller
The time counting runs, as soon as mains voltage is connected (without fault).
If events step on (Motor fault, External Error, etc.), the period of operation is stored at
this time (
Events).
00056:46:13
O
= Operation,
T
= Time,
M
= Motor
The time counting runs as soon as a modulation of the controller is present
DC-Voltage
The intermediate circuit voltage without load is the peak value of the input voltage.
In a three-phase supply network with 400 V, an intermediate circuit voltage of ca. 565 V
results. This voltage sinks slightly under load.
Heatsink
Display of the internal temperature of the power semiconductor. During impermissibly
high levels (at 90
°
C), the output power is automatically reduced. At 105
°
C switch off.
Capacitor
Display of DCLink Elco temperature. During impermissibly high levels (from 75
°
C on),
the output power is automatically reduced.
At 90
°
C switch off.
Filterchoke
Display of sine
fi
lter choke temperature. In case of temperature increase above prede-
termined threshold value the modulation is switched off. Restart when cooled down!
E1-KTY
Signal height at analog input E1 (Analog In 1)
E1-Current
E1-Voltage
Operating Instructions
Fcontrol
–
model series FXDM
Diagnostics menu
L-BAL-E072-GB 1642 Index 008
Part.-No.
90/105