Code
Relay
K1
Explanation
Reaction of device
Adjustment
7
de-energized, 13 -
14 interrupted
ZK undervoltage
Intermediate circuit voltage below a
fi
xed
limit for longer than 75 s.
The modulation is switched off immedi-
ately at undervoltage, error message
after 75 s.
Automatic switching back on and switch-
ing off of error message when the volt-
age exceeds the
fi
xed limit for at least 5
s.
Check line voltage.
8
de-energized, 13 -
14 interrupted
ZK overvoltage
Intermediate circuit voltage above
fi
xed
limit for longer than 75s.
Reason for excessively high line voltage
or alternator motor operation.
The modulation is switched off immedi-
ately at overvoltage, error message after
75 s.
Automatic switching back on and switch-
ing off of error message when the volt-
age drops below the
fi
xed limit for at
least 15 s.
Check line voltage.
Prevent generator motor operation.
9
energized 13 - 14
bridged
IGBT cooling down period
IGBT cooling down period for approx.
60 sec.
Final shutoff after 2 cooling-off intervals
Code 6.
10
de-energized, 13 -
14 interrupted
Communication fault
MODBUS communication interrupted
description MODBUS communica-
tion
12
de-energized, 13 -
14 interrupted
Line voltage too low
Line voltage below a
fi
xed limit for longer
than 75 s.
The modulation is switched off immedi-
ately at undervoltage, error message
after 75 s.
Automatic switching back on and switch-
ing off of error message when the volt-
age exceeds the
fi
xed limit for at least
5 s.
Check line voltage.
13
de-energized, 13 -
14 interrupted
Line voltage too high
Line voltage above
fi
xed limit for longer
than 75 s.
The modulation is switched off immedi-
ately at overvoltage, error message after
75 s.
Automatic switching back on and switch-
ing off of error message when the volt-
age drops below the
fi
xed limit for at
least 15 s.
Check line voltage.
14
de-energized, 13 -
14 interrupted
Error Peak current
If the output current increases above the
speci
fi
ed limit (even in a short time-
frame) the device will switch-off.
After a switch off the controller waits for
30 seconds then the controller attempt a
start.
If 10 switch offs take place consecutively
within 60 s (time to next respective
error),
fi
nal switch off takes place with an
error message.
Should no further switch off be exceeded
in 90 sec. the counter will be reset.
15
de-energized, 13 -
14 interrupted
Motor fault
A connected thermostat or thermistor
has tripped the circuit or interruption be-
tween both terminals
“
TB / TP
”
.
Plug for
“
TB
”
or
“
TP
”
in wrong position.
The unit cuts out and does not switch on
again.
Check motor and connection then reset
(
Motor protection).
16
de-energized, 13 -
14 interrupted
Sine
fi
lter to hot
(only in version with integrated sine
fi
lter)
Switch off at to high temperature, restart-
ing after cooling down.
Check temperature in controller, Check
cooling of the controller.
Operating Instructions
Icontrol Basic
–
model series FSDM2.6...62
Diagnostics / Faults
L-BAL-E160-GB 1701 Index 004
Part.-No.
20/28