5.4 Motor connection

The motor is connected at terminals U1 and U2. Several motors can be connected to the device.

Attention

The maximum total control current (speci

ed for electronic voltage regulation) for all motors

may not exceed the device

s rated current.

If the maximum control current for electronic voltage regulation is not known, a supplementary

20 % of the rated motor current must be allowed for.

When controlling motors from other manufacturers, the controllability and the maximum

current for electronic voltage regulation should be requested from the manufacturer.

Information

It is recommended that a separate motor protection unit be foreseen for each fan.

For motors with thermistors

TB

e.g. type S-ET10.

5.4.1

Running noise

When controlling ventilators using electronic voltage regulators, motor noise can occur (due to the

system), which can be troublesome (Phase cutting = series

P...

).

On fast running ventilators with a high level of air noise, this noise is relatively low. On slow running

ventilators with a low level of air noise, this noise may be dominant in the lower speed range due to

the occurrence of resonance.

For systems where noise is critical, we recommend using our controllers series

STEPcontrol

,

SINUcontrol

or

Fcontrol

5.5 Motor protection

Attention!

Motor thermostats cannot be connected to these controller. I.e. a separate motor protection is

required. We cannot under any circumstances accept liability for damage to the motors which

do not have the required motor protection. It is recommended that every fan is equipped with a

separate motor protection unit e.g. type S-ET10 (

F

connection diagram) !

5.6 Signal or sensor connection (E1 = Analog In 1)

The unit has one-analog input: terminals

E1

/

GND

(Analog In 1).

The connection is independent of the programmed operating mode and from the sensor signal

employed.

The internal jumpers must be placed in correct position depending on input signal. Factory setting 0 -

10 V.

When connecting

passive

temperature sensors TF.. (KTY81-210) must be paid attention to no

polarity.

When connecting

active

sensors attention must be paid to correct polarity, a 24 V DC power

supply is integrated.

For sensors in two-wire-technology (4 - 20 mA signal), the connection is made on the

+24 V

and

E1

(

GND

terminal is omitted).

Over DIP 4 an inverting of the input is possible for mode

1.01

speed controller.

DIP 4 =

|

OFF

|

(factory setting) for signals: 0 - 10 V, 2 - 10 V, 0 - 20 mA, 4 - 20 mA

DIP 4 =

|

ON

|

for signals: 10 - 0 V, 10 - 2 V, 20 - 0 mA, 20 - 4 mA

Attention!

Never apply line voltage to analog inputs!

5.7 Output voltage 10 - 10 V (A = Analog Out)

Constant v10 V e. g. for external potentiometer by operation as speed controller

1.01

.

Connection to terminals

A1

-

GND

=

Analog Out 1

(I

max

10 mA).

It is not permissible to connect outputs of several devices to each other!

Operating Instructions

Acontrol

model series PKE-6 /-10 / PKE-14

Electrical installation

L-BAL-E042-GB 1002 Index002

Part.-No. 00163314-GB

9/26

Summary of Contents for Acontrol PKE-6

Page 1: ...ntrol PKE 6 10 PKE 14 P controller and speed controller for variable voltage 1 fans Operating Instructions Software version D1361A from Version 00 L BAL E042 GB 1002 Index 002 Part No 00163314 GB engl...

Page 2: ...uences during commissioning 7 5 Electrical installation 8 5 1 Safety precautions 8 5 2 EMC compatible installation 8 5 2 1 Motor feeder cable 8 5 2 2 Signal cable 8 5 3 Mains connection 8 5 4 Motor co...

Page 3: ...mperature control Heating function 17 9 3 Pressure control condensers P Controller 3 01 18 9 3 1 Setting for operation as Pressure controller 18 9 3 2 Example Pressure control condensers 18 9 3 3 Sett...

Page 4: ...illustrations or drawings provided Ziehl Abegg AG is not liable for damage due to misuse incorrect use improper use or as a consequence of unauthorized repairs or modi cations 1 4 Copyright These oper...

Page 5: ...Also note the instructions of AEL DLG VdS 2 4 Requirements placed on the personnel due diligence Persons entrusted with the planning installation commissioning and maintenance and servicing in connec...

Page 6: ...tractor or owner must also ensure that the electric systems and equipment are operated and maintained in accordance with electro technical regulations The owner is obliged to ensure that the device ar...

Page 7: ...e on a clean and stable base Do not distort during assembly Use the appropriate mounting devices for proper installation of the unit Do not mount equipment on vibrating base When mounted onto lightwei...

Page 8: ...arance or thermal shielding is required 4 3 Outdoor installation Outdoor installation is possible up to 20 C when the controller supply is not switched off Installation must be protected from the effe...

Page 9: ...astic housing parts because there is no potential equalization Never clean electrical equipment with water or similar liquids Information The respective connections are represented in the enclosure of...

Page 10: ...ection is required We cannot under any circumstances accept liability for damage to the motors which do not have the required motor protection It is recommended that every fan is equipped with a separ...

Page 11: ...ted Attention No disconnection isolation when turned off in accordance with VBG4 6 Never apply line voltage to the digital input It is not permissible to connect inputs of several devices to each othe...

Page 12: ...over n max Potentiometer n max Pband Function dependently on selected mode of operation For speed controller 1 01 Maximal output voltage speed limiter Setting range 100 n min 100 output voltage fully...

Page 13: ...tches Attention Setting of jumper and switches not under voltage Observe the safety notices Changed functions become active partly only after renewed switching on the mains voltage E1 Analog In factor...

Page 14: ...tch S1 Position factory setting for all dipswitches OFF DIP Function OFF ON 1 Selection Speed controller P Controller Speed controller P Controller 2 Minimum speed cut off OFF ON 3 Type of Signal 0 10...

Page 15: ...ON OFF approx 2 5 of 100 set value nM 50 100 I Min Min 35 Max 100 20 C S 7 K R 27 C 2 0 K 10 05 2007 v_min_luft_abschalt vsd Minimum speed cut off idealized principle diagram nM Motor speed S Setpoin...

Page 16: ...priority if over n max 28 08 2008 v_nmax_pband_pke VSD n max P band R 4 9 5 30 n max Pband Maximal output voltage speed limiter Setting range 100 n min 100 output voltage fully clockwise position 30 9...

Page 17: ...mperature control with passive sensors TF KTY Setting range 0 100 26 76 C measuring range of controller Scale 0 100 26 76 C for Temperature control with passive sensors TF KTY set 0 5 10 15 20 25 30 3...

Page 18: ...C n min 35 Idealized principle diagram 9 2 3 Example Temperature control Heating function Val Set n DIP4 ON Temperature sensor type TF Measuring range controller 26 76 C Settings set 50 25 C 102 K 10...

Page 19: ...0 100 5 30 measuring range of sensor 0 100 n min R 4 8 28 08 2008 v_nmin_pke VSD n min Minimum output voltage basic speed Setting range 0 100 n min takes priority if over n max 9 3 2 Example Pressure...

Page 20: ...5 58 41 62 30 65 96 69 41 72 70 75 82 78 81 81 68 84 44 87 09 89 66 R401A C 29 21 6 93 6 40 16 33 24 39 31 26 37 28 42 68 47 59 52 10 56 29 60 22 63 91 67 40 70 72 73 88 76 91 79 81 82 60 85 29 87 99...

Page 21: ...r max imum signal values depending on selected signal type The device works with minimal or maximum modula tion depending on whether there is a short circuit or an interruption and on the programmed m...

Page 22: ...densation Electromagnetic compatibility for the standard voltage 230 400 V according to DIN IEC 60038 Interference emission EN 61000 6 3 domestic household applications Interference immunity EN 61000...

Page 23: ...KTY 4 1 E1 V mA C GND 24 V M 1 PE U1 U2 1 Motor ohne Thermostatschalter without thermostats 2 1 Line 1 230 V 50 60 Hz 2 1 Motor without thermostats 3 Output 0 10 V Imax 10 mA 4 Input 0 10 V 2 10 V 0...

Page 24: ...reglerad spanning 1 60V 250V 50 60Hz 1 2 4 6 12 11 24 23 Option ZB ZK 2S Kontaktbelastung der Hilfskontakte contact rating of auxiliary contacts pouvoir de coupure des contacts auxiliaires Kontaktbel...

Page 25: ...del series PKE 6 10 PKE 14 Enclosure L BAL E042 GB 1002 Index 002 Part No 00163314 GB 24 26 11 3 Dimensions mm PKE 6 PKE 10 PKE 14 Switch off the main supply before removing the cover Vor ffnen des De...

Page 26: ...tance 21 L line fuse 21 M mains is connected 8 mains voltage 8 maximum control current 9 MBG 30I 18 Minimum space requirement 7 Minimum speed cut off 14 Mode 12 motor feed cable 8 motor noise 9 motor...

Page 27: ...e information If you have any technical questions while commissioning or regarding malfunctions please contact our V STE support department for control systems ventilation technology Our worldwide con...

Reviews: