housing parts in metal terminal space covers and housing casings. Commissioning is
only permissible after these screws have been properly attached!
•
The device owner is responsible for the EMC of the entire plant according to the
locally applicable standards.
•
Metal screwed-connections are not permitted in plastic housing parts because there is
no potential equalization.
•
Never clean electrical equipment with water or similar liquids.
Information
The respective connections are represented in the enclosure of this Operating
Instructions (see connection diagram)!
5.2 EMC-compatible installation
5.2.1 Motor cable
The applicable standard for interference emissions is EN 61000-6-3. Compliance with
this standard is achieved through the use of an unscreened motor feed cable.
5.2.2 Control cables
Pay attention to suf
fi
cient distance from powerlines and motor wires to prevent interfer-
ences. The control cable may not be longer than 30 m. Screened control cables must be
used when the cable length is longer than 20 m. When using a shielded cable connect
the shielding to one side only, i.e. only to the control unit with the protective ground (keep
cable short and with as little inductance as possible!).
5.2.3 Harmonics current for devices
≤
16 A
According to EN 61000-3-2 these devices are to be classi
fi
ed as
“
professional
”
devices.
Connection to a low voltage supply (public networks) is allowed insofar as this has been
clari
fi
ed with the respective energy supply company responsible.
Note: up to a maximum current of approx. 4 A, the limits are adhered to with no
restrictions.
Exception for Germany: An energy provider follows the technical connection conditions
of the TAB2007, in which case the use of phase angle controlled devices up to a rating
of 3.4 kVA per phase is allowed.
5.3 Mains connection
The mains connection is made at the terminals: PE, L1 and N. In this regard, it is
essential to ensure that the mains voltage lies within the allowable tolerance speci
fi
ca-
tions (see technical data and rating plate af
fi
xed to the side).
Danger due to electric current
The mains voltage must comply with the DIN EN 50160 quality characteristics and the
de
fi
ned standard voltages in IEC 60038!
Operating Instructions
Acontrol
PSET6 / PSET10
Electrical installation
L-BAL-E141-GB 1925 Index 004
Part.-No.
11/24