1
energized
Terminals 12 - 14
bridged
no enable
Terminals
“
D1
”
-
“
D1
”
(Digital In 1)
not bridged.
Switch OFF by external contact
(
digital input).
2
de-energized
terminals 11 - 12
bridged
Motor fault
Tripping of connected thermostat
or break between terminals
“
TB
”
.
The unit cuts out and does not
switch on again.
Check motor and connection then
reset (
Motor protection).
Code
09.06.2011
v_flash_code_pset.VSD
2
1
ON
OFF
8.1 If controller doesn
´
t work correctly
Information
Setting of dip switches in principle only when device is not under voltage.
If the device is on mains supply modi
fi
cations will partly not be identi
fi
ed and realized.
Attention!
It is generally forbidden to carry out work on electrical live parts. Protection class of the
device when open is IP 00! It is possible to touch hazardous voltages directly.
Operating Instructions
Acontrol
PSET6 / PSET10
Diagnostics / Faults
L-BAL-E141-GB 1925 Index 004
Part.-No.
19/24