Cause
Explanation
Reaction of Controller
Remedial measures
14 x
ON
Error peak current
If the motor current increases
above the speci
fi
ed limit (even in a
short time-frame) the device will
switch-o
ff
.
After a switch o
ff
the controller
waits for 5 seconds then the con-
troller attempt a start.
Arises within 60 sec. in series 5
further disconnections a
fi
nal
switch o
ff
with fault indication fol-
lows.
Should no further switch o
ff
be
exceeded in 60 sec. the counter
will be reset.
17 x
ON
Temperature alarm
Excess of the max. permissible in-
side temperature.
Controller switches o
ff
motor. Au-
tomatic restarting after cooling
down.
Check installation of the device
and cooling of the controller.
*
for factory programmed function: Fault indication inverted
7.3 Behaviour in rotation by air current in reverse direction
In the STOP state (no release, no preset signal, no voltage supply) the motor controller
does not intervene when the fan turns in the wrong direction (e.g. due to a draught).
If the fan is started (= voltage ON), while being driven in the opposite direction to that set,
the speed is reduced controlled to
“
0
”
and restarted in the set direction of rotation.
The higher the speed to be reduced, the longer this process lasts.
Information
Do not disconnect the line voltage if, during an application, this might result in the
disconnected fan being propelled very powerfully in the reverse direction. This ensures a
safe start at all times.
Assembly instructions
ECblue
Diagnostics / Faults
L-BAL-F056-GB 2022/45 Index 005
Part.-No. 00700562-GB
36/44