Prior to installing the fan, it is to be checked whether the safety zone as per EN ISO
13857 and in household appliances as per EN 60335 are met. If the installation height
(danger zone) above the reference level is greater than or equal to 2700 mm and is
not reduced by auxiliary means such as chairs, ladders, work platforms or bases on
vehicles, a guard grille against accidental contact is not necessary at the fan.
•
If the fan is located in danger zone, then the manufacturer or operator shall ensure
that hazards shall be prevented by appropriare protective constuctions which meet
the requirements to EN ISO 13857.
•
Protective measures must be taken against falling parts when mounting with a
hanging rotor.
•
The custom designs must suit the prevailing conditions.
•
Tighten the fastenings with the speci
fi
ed torques.
•
Do not allow drilling chips, screws and other foreign bodies to reach the device
interior!
•
Any use below -10
°
C is dependent on not being subjected to unusual, sudden or
mechanical loads or stresses on the material (min. ambient temperature
Technical
data).
•
Corrosion is possible at the cutting edges on sendzimir galvanised parts.
•
Before the
fi
rst switch-on, remove any items that may be present (borings, screws and
other foreign objects) from the intake area - risk of injury from any objects that may
fl
y
out!
4.2 Connecting lead, position terminal compartment
Information
In demanding environments (wet areas, open air installation) all connections must
incorporate water drainage curves. To ensure that water cannot penetrate through to the
controller housing from the connections install a terminal box lower than the fan.
In vertical mounting (installation position
“
H
”
= motor shaft horizontal), install the fan for
protection ahainst penetrating moisture with the terminal compartment vertically
downwards (up to max. 30
°
lateral inclination).
Optimum heat dissipation of the power loss resulting in the device is achieved in this
position (
Diagnostic/ Faults / Temperature Management).
Quick Start Guide
ECblue
Mounting
L-BAL-F055-GB 1634 Index 004
Part.-No. 00700561-GB
9/23