5.2
Version with connection cables
Information
•
In versions with connecting leads the connection is made to the colour coded wires. Note the cable
bands on the connecting leads and the respective connection diagram.
•
The type, length, colour coding and connection assignment of the connecting leads may vary
depending on the version.
•
Read the following chapter
“
Version without connection cables
”
for a new connection to the
terminals in the terminal compartment.
ECblue BASIC connection version example
1 ~ ECblue, for line and relay: hose cable 5 x 1.5 mm
2
(LiF9Y11Y-JB)
BN
BU
GNYE
WH
WH
brown
L1
Voltage supply
blue
N
green-yellow
PE
white
11
Relay
white
14
K1
3 ~ ECblue, for line and relay: hose cable 6 x 1.5 mm
2
(LiF9Y11Y-JB)
BK
GNYE
WH
WH
BN
BU or GY
brown
L1
Voltage supply
blue or grey
L2
black
L3
green-yellow
PE
white
11
Relay
white
14
K1
1 ~ and 3 ~ ECblue, for control: hose cable 5 x 0.5 mm
2
(LiF9Y11Y-0B)
YE
BU
GN
RD
BN
yellow
E1
Analog In 1
blue
GND
green
D1
Digital In 1
red
10V
DC Out
brown
24V
DC Out
Assembly instructions
ECblue BASIC-MODBUS, ECblue BASIC
Electrical installation
L-BAL-F079D-GB 2044 Index 002
Part.-No.
22/80