9.4
Menu group Controller Setup
Controller Setup
9.4.1
Controlmode
Type of device modulation.
0
Factory setting
Control by external signal (0 - 10 V / PWM) at the input
“
E1
”
.
Switching to
fi
xed speed
“
Default Internal2
”
or
“
Default Internal3
”
via digital input
possible (see IO Setup).
1
Speed control register h2 (absolute)
Example: setting 500
500 rpm
2
Speed control register h2 (fractional 0 - 32767 = 0 - 100 %) *
Example: setting 16383
50 % of rated speed
Switching to
fi
xed speed
“
Default Internal2
”
or
“
Default Internal3
”
via digital input
possible (see IO Setup).
3
Speed control register h2 (fractional 0 - 100 = 0 - 100 %) *
Example: setting 50
50 % of rated speed
4
constant speed
“
Set Internal1
”
.
Switching to
fi
xed speed
“
Default Internal2
”
or
“
Default Internal3
”
via digital input
possible (see IO Setup).
5
Fixed speed
“
Default Internal2
”
(without switching possibility to other default).
6
Fixed speed
“
Default Internal3
”
(without switching possibility to other default).
7
Control by E1 (quadratic characteristics)
8
Control by E1 (custom characteristics)
9
Control by E1 (air
fl
ow control)
10
Speed control register h2 (fractional; air
fl
ow control)
11
Speed control register h2 (quadratic characteristics)
12
Speed control register h2 (fractional; custom characteristics)
13
Control by external signal (4 - 20 mA) at the input
“
E1
”
.
14
Control by E1 (constant moment)
15
Speed control register h2 (fractional; constant moment)
*
These functions can only be read using the hand held terminal; programming is only possible using the ZAset Mobile app or
using the ZAset software.