9.2.2
Settings for operation modes
2.01
...
2.05
2.01
Temperature control simple
2.02
Temperature control depending on outdoor temperature (Special function: Sensor connection at
“
E2
”
,
display and setting under
“
E1
”
).
2.03
Temperature control with pre-programmed additional functions (heating, shutter, temperature monitoring).
2.04
Temperature control with 2 sensors
Comparison with control to higher value
“
E2 Function
”
set to comparison
|
4E
|
. Display during operation:
“
Control value
”
Alternative: Average calculation of 2 measuring places
“
E2 Function
”
set to
|
3E
|
. Display during oper-
ation:
“
Average E1 / E2
”
2.05
Temperature control with 2 sensors, regulation on difference temperature.
Display during operation:
“
Value of E1 - E2
”
in K,
“
E1
”
= reference temperatur,
“
E2
”
causes positiv (E2 <
E1) or negative (E2 >E 1) difference.
Setting
Setting
Setpoint1
Setpoint1
Setting range: with passive sensor type
“
TF..
”
: -27.0...75
°
C
Factory setting:
2.01
,
2.03
,
2.04
: 20.0
°
C
at
2.02
: 5.0
°
C
at
2.05
: 0.0
°
C
Setting range: at active sensor type
“
MTG-120V
”
: -10.0...+120.0
°
C
Factory setting:
2.01
-
2.05
: 55.0
°
C
Setpoint 2
Setpoint 2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switch over Setpoint 1/2 by external contact (as long as no allocation is carried out:
Display:
|
- - - - -
|
IOSetup).
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
passive Sensor type
“
TF..
”
Setting range: 0-120.0 K (Kelvin)
Factory setting: 5.0 K, (at
2.02
: 20.0 K)
active Sensor type
“
MTG-120V
”
Setting range: -120.0...+120.0 K
Factory setting: 65.0 K
Min. Speed
Min. Speed
(basic speed only when needed)
Setting range:
|
OFF
|
→
“
Shutdown Freq.
”
(
Motor Setup) -
“
Max. Speed
”
.
Factory setting:
|
OFF
|
Max. Speed
Max. Speed
(speed limitation only when needed)
Setting range:
“
Max. Frequency
”
(
Motor Setup) -
“
Min. Speed
”
Factory setting: 50.0 Hz
Manual mode
Manual mode
“
OFF
”
= automatic control as function of the set parameters (Factory setting)
“
ON
”
= automatic control without function, speed setting in menu
“
Speed manual
”
Speed manual
Speed manual
Manual speed setting without in
fl
uence by the external signal.
Activation by menu
“
Manual mode
”
or external contact at digital input (
IO Setup).
Setting range: 0...
“
Max. Frequency
”
(
Motor Setup)
Factory setting: 50.0 Hz
For information about deactivated regulation the adjusted value for manual speed is
indicated alternating with the actual value.
Operating Instructions
Fcontrol
–
model series FXDM
Programming
L-BAL-E072-GB 1642 Index 008
Part.-No.
37/105