9.11
Limits
9.11.1
Limit indication depending on modulation
Controller function
Following functions can be allocated to the limit indication
OFF
no function
1L
Indication with the centralized fault of a programmed relay (IO allocation
Function
|
2K
|
).
Warning symbol in display,
“
AL
”
code in events memory.
2L
Is merely displayed in the events menu as message
“
msg
”
.
In the IO setup, a separate relay can be allocated independent of these settings.
Level min.
If the modulation exceeds the set
“
Modulation max
”
value, this is reported until the set
value
“
Modulation min
”
has been undercut.
Setting range
“
Modulation min.
”
:
“
Min. Speed
”
-
“
Modulation max.
”
Setting range
“
Modulation max.
”
:
“
Modulation min.
”
-
“
Max. Speed
”
The indication is delayed by the time set in
“
Display delay
”
.
Level max.
Level Delay
Time delay exceeding
“
Modulation max.
”
up to indication by relay and alarm symbol.
Setting range: 0 - 120 sec.
Factory setting: 2 sec.
Example indication by relay
“
K1
”
:
not inverted
IO Setup: K1 Function = 4K
IO Setup: K1 Inverting = OFF
Inverting
IO Setup: K1 Function = 4K
IO Setup: K1 Inverting = OFF
min
max
100 %
A
0
1
min
max
100 %
0
1
11.05.2007
v_grenzwert_ausst_k1_ni.vsd
A
A
Modulation
min
max
100 %
0
1
min
max
100 %
0
1
11.05.2007
v_grenzwert_ausst_k1_i.vsd
A
A
A
Modulation
If
“
Level min.
”
is higher than
“
Level max.
”
, the
“
Level max.
”
switching point is without hysteresi.
9.11.2
Limit indication depending on setting or sensor signal
Lmt E1 Function
Following functions can be allocated to the limit indication
OFF
no function
1L
Indication with the centralized fault of a programmed relay (IO allocation
Function
|
2K
|
).
Warning symbol in display,
“
AL
”
code in events memory.
2L
Is merely displayed in the events menu as message
“
msg
”
.
In the IO setup, a separate relay can be allocated independent of these settings.
Operating Instructions
Fcontrol
–
model series FXDM
Programming
L-BAL-E072-GB 1642 Index 008
Part.-No.
72/105