OFF
No function
Relays remain always de-energized
Operating indication
(1K)
Operating indication (factory setting for
“
K1
”
, non inverting).
Operation without fault, reports enable
“
OFF
”
Fault indication
(2K)
Fault indication (factory setting for
“
K2
”
, non inverting).
Pulled up in operation without fault, with release
“
OFF
”
not dropped out.
Drops out in case of line and device fault and external fault at the digital input. Depend-
ing on programming in event of sensor failure.
External error
(3K)
External fault separate with message at digital input (factory setting if terminals
bridged)
Limit modulation
(4K)
Limit modulation
Over or falling below limits for modulation
Limit E1
(5K)
Limit
“
E1
”
When over or falling below limits for input signal
“
E1
”
Limit E2
(6K)
Limit
“
E2
”
When over or falling below limits for input signal
“
E2
”
For modes as controller higher
2.01
Setpoint Offset
(7K)
Setpoint Offset
Deviation between actual value and setpoint to high
Group2
(8K)
Group control (Group 2)
Switching on fans depending on modulation
Group3
(12K)
Group control (Group 3)
Switching on fans depending on modulation
Group4
(14K)
Group control (Group 4)
Switching on fans depending on modulation
For modes as temperature controller with additional functions
2.03
2.Heating
(9K)
Heating function
Switch ON point: temperature = Se/- Offset
Switch OFF point: Temperature around hysteresis over switch ON point
2.Cooling
(10K)
Cooling function
Switch ON point: temperature = Se/- Offset
Switch OFF point: Temperature around hysteresis below switch ON point
Limits GW E1 and GW E2
Function
Description function GW E1, GW E2
OFF
no function
Failure
(1L)
Indication with the centralized fault of a programmed relay (IO allocation Function
|
2K
|
).
Warning symbol in display,
“
AL
”
code in events memory.
Message
(2L)
Is merely displayed in the events menu as message
“
msg
”
.
Filter error
(3L)
Like function
|
1L
|
with fault message
“
Filter
”
Filter Message
(4L)
Like function
|
2L
|
with fault message
“
Filter
”
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Menu tables
L-BAL-E212-GB 1451 Index 003
Part.-No.
111/123