5.11
Add-on module type Z-Modul-B Part-No. 380052
The add-on module can be retro
fi
tted as required. This may be necessary when the analog and digital
outputs and inputs are insuf
fi
cient for certain applications. The board is easy to install in the device
and is connected to the printed circuit board (X13) with the plug. The additional outputs and inputs are
programmed in the menu group
“
IO Extension
”
, this appears automatically after the menu group
“
IO
Setup
”
if an add-on module is installed.
Information
The clock module type Z-Module-RTC and the add-on module type Z-MODULE-B both need the slot
|
X13
|
. That means that only one of the two modules can be used!
Add-on module type Z-
Modul-B
•
1x analogue input 0-10 V (R
i
> 100 k
Ω
) for external Set point
•
1x output 0 - 10 V (I
max
10 mA)
•
3x digital-inputs, Activation via
fl
oating contacts
•
2x relay outputs (contact load 2 A 250 V AC)
5.12
Digital inputs (D1, D2)
Various functions can be allocated to the digital inputs
“
D1
”
and
“
D2
”
(
IO Setup: Functions summary
of the digital inputs). Activation via
fl
oating contacts (a low voltage of ca. 24 V DC is connected).
Danger due to electric current
Never apply line voltage to the digital input!
Observe input resistance and voltage range (
Technical data).
5.13
Relay outputs (K1, K2)
Various functions can be allocated to the relay outputs
“
K1
”
and
“
K2
”
(
IO Setup: function and
inverting relais outputs). Max. contact rating
technical data and connection diagram.
Relays K1
•
Connection of the
fl
oating contacts of relay
“
K1
”
to the terminals 11, 14, 12.
•
“
K1 Function
”
factory setting:
|
1K
|
=
Operating indication
. I.e. energized for operation without
fault, for enable
“
OFF
”
de-energized.
Relays K2
•
Connection of the
fl
oating contacts of relay
“
K2
”
to the terminals 21, 24, 22.
•
“
K2 Function
”
factory setting:
|
2K
|
=
Fault indication
. I.e. energized for operation without fault and
for enable
“
OFF
”
.
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Electrical installation
L-BAL-E212-GB 1451 Index 003
Part.-No.
17/123