9.10.2.3
External fault Function
|
2D
|
Connecting an external alarm indication (via
fl
oating contact). The device continues to work un-
changed during an external indication to the digital input; the alarm symbol appears in the display.
This indication can be issued via the relay contacts (K1 K2) (
IO Setup function K1, K2).
Example for connecting an external alarm indication e.g. to digital input
“
Digital In 1
”
Controller
1~ S-ET..
3~ STDT..
TB
TB
TB
K1
D1
D1
10.05.2007
v_2d_externe_stoerung_set_stdt.vsd
1~ S-ET..
3~ STDT..
1~ S-ET..
3~ STDT..
Info
•
Indication during closed contact (factory setting):
“
D1 Inverting
”
=
“
OFF
”
•
Indication during opened contact:
“
D1 Inverting
”
=
“
ON
”
Alternative display texts for error message
Controller Setup / display text for
external message.
External error
Display alternating with ac-
tual value display
9.10.2.4
Limit ON / OFF, Function
|
3D
|
The value for
“
Limit
”
adjusted in the Controller Setup, is activated over a digital input.
Contact e.g. at ditgital input
“
Digital In 1
”
(depending on device type at terminals
“
D1
”
-
“
D1
”
or
“
D1
”
-
“
24 V
”
).
For
“
D1 Inverting
”
=
“
OFF
”
, limitation active at closed contact.
The limitation in
fl
uences both outputs in operation with two control circuits.
Controller
24V
D1 D1
1
0
n = 0- 80 %
1
0
- - - - -
n = 0- 100 %
10.05.2007
v_3d_limit.vsd
1
1
Setting
“
Limit
”
(depending on device type in: %, Hz, rpm)
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
70/123